MAN0292-08

10 NOV 2006

PAGE 5

MIX902

This Data Sheet is published individually & also as a part of the SmartStack Supplement (SUP0246-05).

Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.

2. For Analog Outputs: The default sets the output values to zero when the controller enters idle/stop
mode. By selecting the Module Setup tab, each output can be set to a specific value or hold the last
value. Generally, most applications use the default settings.

Warning: The default sets the output values to zero when the controller enters idle/stop mode.
To avoid injury of personnel or damages to equipment, exercise extreme caution when
changing the default setting using the Module Setup tab.

3. For Analog Inputs:

Filter Constant sets the level of digital filtering according to the following chart.

I/O Map Tab

The I/O Map describes which I/O registers are assigned to a specific SmartStack

™ Module and where the

module is located in the point map. The I/O Map is determined by the model number and location within
the SmartStack

™. The I/O Map is not edited by the user.

Digital Filtering. The illustration above demonstrates the effect of digital filtering (set with Fillter
Constant) on module response to a temperature change.

60

20

100

40

80

20

0

10

100

90
80
70
60
50
40
30

Scans

0

1

2

3

4

5

6

0

7

%

C

om

pl

e

te

[

]

Filter
Constant