4.1 POWER WIRING

1

2

AC/DC

AC/DC

4.2 VOLTAGE/RESISTANCE/CURRENT INPUT SIGNAL WIRING

IMPORTANT: Before connecting signal wires, the Input Range Jumpers and Excitation Jumper should be verified for proper position.

Process/Current

Signal

(external powered)

Voltage Signal

Process/Current Signal

(2 wire requiring 18V

excitation)

Excitation Jumper: 18 V

6

7

8

+

̶

200VDC MAX.

V-

TC

-R

TD I

N

I INPU

T

INP COMM

Current Signal (3 wire

requiring 18 V excitation)

Terminal 3: +Volt supply

Terminal 6: +ADC (signal)

Terminal 8: -ADC (common)

Excitation Jumper: 18 V

Voltage Signal (3 wire

requiring 18 V excitation)

Terminal 3: +Volt supply

Terminal 7: +VDC (signal)

Terminal 8: -VDC (common)

Excitation Jumper: 18 V

6

8

2A DC MAX.

I INPU

T

INP COMM

Load

-

+

-

+

Resistance Signal

(2 wire requiring

excitation)

Terminal 3: Jumper to

terminal 7

Terminal 7: Resistance
Terminal 8: Resistance
Excitation Jumper:

1.05 mA REF.

T/V Jumper: V position
Voltage/Resistance Input

Jumper: Set per input signal

3

7

8

V EX

C

INP COMM

V-TC-RTD-I

N

1.05 mA

REF.

10K MAX

Potentiometer Signal as Voltage Input

(3 wire requiring excitation)

Terminal 3: High end of pot.
Terminal 7: Wiper
Terminal 8: Low end of pot.
Excitation Jumper: 2 V REF.
T/V Jumper: V
Voltage/Resistance Input Jumper: 2 Volt
Module 1 Input Range: 2 Volt

Note: The Apply signal scaling style

should be used because the signal

will be in volts.

6

7

8

3

V-TC-RTD-I

N

I INPU

T

V EX

C

INP COMM

+

3 WIRE TRANSMITTER

_

Vout

Iout

3

7

8

Rmin=1KΩ

V EX

C

INP COMM

V-TC-RTD-I

N

2V REF.

2V

INPUT

5

6

3

RT

D EX

C

V EXEC

I INPU

T

2 WIRE

TRANSMITTER

-

+

4

COMM

CAUTION: Sensor input common is NOT isolated from user input common. In order to preserve the safety of the controller application, the sensor input

common must be suitably isolated from hazardous live earth referenced voltages; or input common must be at protective earth ground potential. If not,

hazardous live voltage may be present at the User Inputs and User Input Common terminals. Appropriate considerations must then be given to the

potential of the user input common with respect to earth common; and the common of the isolated plug-in cards with respect to input common.

4.3 TEMPERATURE INPUT SIGNAL WIRING

IMPORTANT: Before connecting signal wires, verify the T/V Jumper is in the T position.

3-Wire RTD

Thermocouple

2-Wire RTD

5

7

8

RTD EX

C

V-TC-RTD-I

N

INP COMM

Sense Lead

Jumper

5

7

8

RTD EX

C

V-TC-RTD-I

N

INP COMM

Sense Lead

RTD (Excitation)

7

8

+

̶

V-TC-RTD-I

N

INP COMM

CAUTION: Sensor input common is NOT isolated

from user input common. In order to preserve the

safety of the controller application, the sensor

input common must be suitably isolated from

hazardous live earth referenced voltages; or input

common must be at protective earth ground

potential. If not, hazardous live voltage may be

present at the User Inputs and User Input Common

terminals. Appropriate considerations must then be

given to the potential of the user input common with

respect to earth common; and the common of the

isolated plug-in cards with respect to input common.

1

2

AC/DC

AC/DC

+

-

1

2

AC/DC

AC/DC

+

-

OR

AC Power

DC Power

The power supplied to the meter shall employ a 15 Amp UL approved circuit breaker for AC input and a 1 Amp, 250 V UL approved fuse for DC input. It shall be

easily accessible and marked as a disconnecting device to the installed unit. This device is not directly intended for connection to the mains without a reliable means

to reduce transient over-voltages to 1500 V.