Type, Asgn, Anlo – Red Lion PAX2C User Manual
Page 18: Anhi, Updt, Iflt, Anlg ), None, O u t, A n l g
18
Analog
Output Type
Analog
Output
Assignment
Analog
Low Scale
Value
Analog
High Scale
Value
Analog
Update
Rate
Probe
Burn-out
Action
F1
F2
P
D
Pro
N O
Pro
O u t
Out
P2C
A n L G
tYPE
AnL
4 - 2 0
mA
ASGN
AnL
N O N E
ANLO
AnL
0
ANHI
AnL
1 0 0 O
UPdt
AnL
0 . 0
SEC
IFLt
AnL
L o
(Temp Only)
This section is only accessible with the optional PAXCDL Analog card installed (see Ordering Information).
ANALOG OUTPUT TYPE
4-20
0-10
0-20
Enter the analog output type. For 0-20 mA or 4-20 mA use
terminals 18 and 19. For 0-10 V use terminals 16 and 17. Only one
range can be used at a time.
ANALOG OUTPUT ASSIGNMENT
NONE
INPt
HI
LO
OP
SP
dEv
Enter the source for the analog output to retransmit:
NONE
= Manual Mode operation. (See Serial RLC
Protocol in the Communications Port module).
INPt
= Input Value
HI
= Maximum Display Value
LO
= Minimum Display Value
OP
= Output Power
SP
= Active Setpoint Value
dEv
= Deviation from the Setpoint value
ANALOG LOW SCALE VALUE
-1999
to
9999
Enter the Display Value that corresponds to 0 mA (0-20 mA), 4
mA (4-20 mA) or 0 VDC (0-10 VDC).
ANALOG HIGH SCALE VALUE
-1999
to
9999
Enter the Display Value that corresponds to 20 mA (0-20 mA) , 20
mA (4-20 mA) or 10 VDC (0-10 VDC).
ANALOG UPDATE TIME
0.0
to
10.0
seconds
Enter the analog output update rate in seconds. A value of 0.0
allows the meter to update the analog output at the ADC Conversion
Rate.
The following programming step is only available when Input Type in the
Input Menu is set for a temperature input (TC/RTD).
PROBE BURN-OUT ACTION
Lo
Hi
Enter the probe burn-out action. In the event of a temperature
probe failure, the analog output can be programmed for low or high
scale.