Eneral, Ontroller, Pecifications – Red Lion PAX2C User Manual
Page 3
3
g
eneral
C
OnTrOller
s
peCifiCaTiOns
1. DISPLAY: Negative image LCD with tri-color backlight.
The display is divided into seven independently programmable color zones:
Line 1, Line 2, Universal Annunciators (1-4) & Mnemonics
Line 1 and 2: 4 digits each line
Display Range: -1999 to 9999
Units - Programmable 3 digit units annunciator
Bar Graph - Programmable 8 segment bar graph
Universal Annunciator 1 thru 4: Programmable 2 digit annunciator
Status Mnemonics: MAN - Controller is in Manual Mode
REM – Controller is in Remote Mode
Vertical Model Digit Size: Line 1 - 0.51" (13 mm), Line 2 - 0.44" (11.2 mm)
Horizontal Model Digit Size: Line 1 - 0.62" (15.7 mm), Line 2 - 0.47" (12.0 mm)
2. POWER:
AC Power: 40 to 250 VAC, 50/60 Hz, 20 VA
DC Power: 21.6 to 250 VDC, 8 W
Isolation: 2300 Vrms for 1 min. to all inputs and outputs.
3. KEYPAD: 2 programmable function keys, 4 keys total
4. A/D CONVERTER: 24 bit resolution
5. DISPLAY MESSAGES:
“OLOL” - Appears when measurement exceeds + signal range.
“ULUL” - Appears when measurement exceeds - signal range
“Shrt” - Appears when shorted sensor is detected. (RTD range only)
“OPEN” - Appears when open sensor is detected. (TC/RTD range only)
“. . . . ” - Appears when display values exceed + display range.
“- . . . ” - Appears when display values exceed - display range.
6. INPUT CAPABILITIES:
Current Input:
INPUT RANGE
ACCURACY *
(18 to 28°C)
ACCURACY *
(0 to 50°C)
IMPEDANCE
‡
RESOLUTION
± 250 µADC
0.03% of rdg
+ 0.03µA
0.12% of rdg
+ 0.04µA
1.11 K
W
0.1µA
± 2.5 mADC
0.03% of rdg
+ 0.3µA
0.12% of rdg
+ 0.4µA
111
W
1µA
± 25 mADC
0.03% of rdg
+ 3µA
0.12% of rdg
+ 4µA
11.1
W
10µA
± 250 mADC 0.05% of rdg
+ 30µA
0.12% of rdg
+ 40µA
1.1
W
0.1mA
± 2 ADC
0.5% of rdg
+ 0.3mA
0.7% of rdg
+ 0.4mA
0.1
W
1mA
Voltage Input:
INPUT RANGE
ACCURACY *
(18 to 28°C)
ACCURACY *
(0 to 50°C)
IMPEDANCE
‡
RESOLUTION
± 250 mVDC
0.03% of rdg
+ 30µV
0.12% of rdg
+ 40µV
451 K
W
0.1mV
± 2.0 VDC
0.03% of rdg
+ 0.3mV
0.12% of rdg
+ 0.4mV
451 K
W
1mV
± 10 VDC
0.03% of rdg
+ 3mV
0.12% of rdg
+ 4mV
451 K
W
1mV
± 25 VDC
0.03% of rdg
+ 3mV
0.12% of rdg
+ 4mV
451 K
W
10mV
± 100 VDC
0.3% of rdg
+ 30mV
0.12% of rdg
+ 40mV
451 K
W
0.1V
± 200 VDC
0.3% of rdg
+ 30mV
0.12% of rdg
+ 40mV
451 K
W
0.1V
Temperature Inputs:
Scale: °F or °C
Offset Range: -1999 to 9999 display units.
Thermocouple Inputs:
Input Impedance: 20MW
Lead Resisitance Effect: 0.03 µV/W
Max Continuous Overvoltage: 30 VDC
INPUT
TYPE
RANGE
ACCURACY*
(18 to 28 °C)
ACCURACY*
(0 to 50 °C) STANDARD
WIRE COLOR
ANSI
BS 1843
T
-200 to 400°C
1.2°C
2.1°C
ITS-90
(+) blue
(-) red
(+) white
(-) blue
E
-200 to 750°C
1.0°C
2.4°C
ITS-90
(+) purple
(-) red
(+) brown
(-) blue
J
-200 to 760°C
1.1°C
2.3°C
ITS-90
(+) white
(-) red
(+) yellow
(-) blue
K
-200 to 1250°C
1.3°C
3.4°C
ITS-90
(+) yellow
(-) red
(+) brown
(-) blue
R
0 to 1768°C
1.9°C
4.0°C
ITS-90
no
standard
(+) white
(-) blue
S
0 to 1768°C
1.9°C
4.0°C
ITS-90
no
standard
(+) white
(-) blue
B
150 to 300°C
300 to 1820°C
3.9°C
2.8°C
5.7°C
4.4°C
ITS-90
no
standard
no
standard
N
-200 to 1300°C
1.3°C
3.1°C
ITS-90
(+) orange
(-) red
(+) orange
(-) blue
C
(W5/W26) 0 to 2315°C
1.9°C
6.1°C
ASTM
E988-90**
no
standard
no
standard
RTD Inputs:
Type: 3 or 4 wire, 2 wire can be compensated for lead wire resistance
Excitation current: 100 ohm range: 136.5 µA ±10%
10 ohm range: 2.05 mA ±10%
Lead resistance: 100 ohm range: 10 ohm/lead max.
10 ohm range: 3 ohms/lead max.
Max. continuous overload: 30 VDC
INPUT TYPE
RANGE
ACCURACY*
(18 to 28 °C)
ACCURACY*
(0 to 50 °C)
STANDARD
**
100 ohm Pt
alpha = .00385
-200 to 850°C
0.4°C
1.6°C
IEC 751
100 ohm Pt
alpha = .00392
-200 to 850°C
0.4°C
1.6°C
no official
standard
120 ohm Nickel
alpha = .00672
-80 to 259°C
0.2°C
0.5°C
no official
standard
10 ohm Copper
alpha = .00427
-110 to 260°C
0.4°C
0.9°C
no official
standard
Resistance Inputs:
INPUT
RANGE
ACCURACY *
(18 to 28°C)
ACCURACY *
(0 to 50°C) COMPLIANCE
MAX CONT.
OVERLOAD
‡
RESOLUTION
100 ohm 0.05% of rdg
+0.03 ohm
0.2% of rdg
+0.04 ohm
0.175 V
30 V
0.1 ohm
999 ohm 0.05% of rdg
+0.3 ohm
0.2% of rdg
+0.4 ohm
1.75 V
30 V
1 ohm
9999 ohm 0.05% of rdg
+1 ohm
0.2% of rdg
+1.5 ohm
17.5 V
30 V
1 ohm
‡
Higher resolution can be achieved via input scaling.
*
After 20 min. warm-up, @ 5 samples per second input rate. Accuracy is
specified in two ways: Accuracy over an 18 to 28ºC and 15 to 75% RH
environment; and Accuracy over a 0 to 50ºC and 0 to 85% RH (non
condensing) environment. The specification includes the A/D conversion
errors, linearization conformity, and thermocouple ice point compensation.
Total system accuracy is the sum of controller and probe errors. Accuracy
may be improved by field calibrating the controller readout at the
temperature of interest.
**
These curves have been corrected to ITS-90.