beautypg.com

Port ), Port, Arameters – Red Lion PAX2C User Manual

Page 39: Usb p, Usb ), Serl ), Cnfg, Type, Baud, Data

background image

39

p

OrT

p

arameTers

(Port)

PORT PARAMETER MENU SELECTION

USb

SErL

Select the Communication Port Mode.

Port

SRL

USb

usb p

OrT

p

arameTers

(USb)

USB

Setup

F1

F2

P

D

Pro

N O

Pro

P o r t

Port

SRL

U S b

USb

SRL

C N F G

USB SETUP

CNFG

SErL

CNFG

= Configures USB with settings required to operate

with Crimson configuration software. This will

automatically internally configure the PAX2C USB

port to use Modbus RTU protocol, 38400 baud, 8

bits, and unit address of 247. The serial port settings

in the Serial Parameters (SErL) will not change, or

show this.

SErL

= Configures USB to utilize serial settings and

protocol as configured in the Serial Parameters.

USb

SRL

CNFG

s

erial

p

OrT

p

arameTers

(SErL)

Communications

Type

Baud

Rate

Data

Bit

Parity

Bit *

Meter

Unit Address

Transmit

Delay

Abbreviated

Printing

Print

Options

F1

F2

P

D

Pro

N O

Pro

P o r t

Port

SRL

S E r L

tYPE

SRL

A S C

bAUd

SRL

3 8 . 4 k

dAtA

SRL

8

PArb

SRL

N O

Addr

SRL

2 4 7

dLAY

SRL

0 . 0 1 0

SEC

Abrv

SRL

N O

OPt

SRL

N O

RLC Mode

Only

COMMUNICATIONS TYPE

ASC

= Modbus ASCII

rLC

= RLC Protocol (ASCII)

rtu

= Modbus RTU

Select the desired communications protocol. Modbus is preferred

as it provides access to all meter values and parameters. Since the

Modbus protocol is included within the PAX2C, the PAX Modbus

option card, PAXCDC4, should not be used. The PAXCDC1 (RS485), or

PAXCDC2 (RS232) card should be used instead.

BAUD RATE

1200

2400

4800

9600

19.2k

38.4k

Set the baud rate to match the other serial communications

equipment on the serial link. Normally, the baud rate is set to the

highest value that all the serial equipment are capable of transmitting

and receiving.

DATA BIT

7

8

Select either 7 or 8 bit data word lengths. Set the word length to

match the other serial communications equipment on the serial link.

PARITY BIT *

NO

EUEN

Odd

Set the parity bit to match that of the other serial communications

equipment on the serial link. The meter ignores the parity when

receiving data and sets the parity bit for outgoing data. If no parity is

selected with 7 bit word length, an additional stop bit is used to force

the frame size to 10 bits.

* Available when Data Bit = 7.

tYPE

SRL

ASC

bAud

SRL

38.4k

dAtA

SRL

8

PArb

SRL

NO