beautypg.com

Hyst, Dead, Pid p – Red Lion PAX2C User Manual

Page 35: Onof ), P i d, O n o f

background image

35

On/Off

Hysteresis

On/Off

Deadband

F1

F2

P

D

Pro

N O

Pro

P i d

Pid

O N O F

HYSt

0 . 2

°F

dEAd

0 . 0

°F

pid p

arameTers

: O

n

/O

ff

p

arameTers

(ONOF)

ON/OFF HYSTERESIS

0

to

50.0

units

The On/Off Hysteresis property is used to eliminate output chatter

by separating the on and off points of the output(s) when performing

on/off control. The hysteresis value is centered around the setpoint,

that is, the transition points of the output will be offset above and

below the setpoint by half of the On/Off Hysteresis value. This value

effects outputs programmed for Heat or Cool. During auto-tune, the controller

cycles the process through 4 on/off cycles, so it is important to set the On-Off

Hysteresis to an appropriate value before initializing auto-tune.

ON/OFF DEADBAND

-199.9

to

999.9

units

The On-Off Deadband property provides a means of offsetting the

on-points of heat and cool outputs programmed for on/off operation.

This results in a deadband if the value is positive, and overlap if the

value is negative. When determining the actual transition points of

the outputs, the On/Off Hysteresis value must also be taken into

consideration.

HYSt

0.2

dEAd

0.0