Disp, Hi-t, Lo-t – Red Lion PAX2C User Manual
Page 30: Hilo ), Code, Code ), D i s p, H i l o, C o d e
30
MAX Capture
Delay Time
MIN Capture
Delay Time
F1
F2
P
D
Pro
N O
Pro
d I S P
dISP
H I L O
Hi-t
SCN
1 . 0
SEC
LO-t
SCN
1 . 0
SEC
d
isplay
p
arameTers
: d
isplay
m
in
/m
aX
C
OnfiguraTiOn
(HILO)
MAX CAPTURE DELAY TIME
0.0
to
25.0
seconds
When the Input Display is above the present MAX value for the
entered delay time, the controller will capture that display value as
the new MAX reading. A delay time helps to avoid false captures of
sudden short spikes.
MIN CAPTURE DELAY TIME
0.0
to
25.0
seconds
When the Input Display is below the present MIN value for the
entered delay time, the controller will capture that display value as
the new MIN reading. A delay time helps to avoid false captures of
sudden short spikes.
HI-t
SCN
1.0
SEC
LO-t
SCN
1.0
SEC
Programming
Security Code
F1
F2
P
D
Pro
N O
Pro
d I S P
dISP
C O d E
COdE
dSP
0
d
isplay
p
arameTers
: s
eCuriTy
C
Ode
C
OnfiguraTiOn
(COdE)
PROGRAMMING SECURITY CODE
0
to
250
The Security Code determines the programming mode and the
accessibility of programming parameters. This code can be used
along with the Program Mode Lock-out (PLOC) in the User Input
Function parameter (Input [User] module).
To activate the Hidden Parameter display loop, a security code
(1-250) must be entered. If a “0” security code is programmed, Full Programming
Mode is available following the Parameter Loop. Pressing the
P key takes you
into, and is used to step through the Parameter Loop. Two modes are available.
Full Programming mode allows all parameters to be viewed and modified.
Parameter display loop mode provides access to those selected parameters that
can be viewed and/or modified without entering the Full Programming mode.
The following chart indicates the levels of access based on various CodE and
User Input PLOC settings.
SECURITY
CODE
USER INPUT
CONFIGURED
USER INPUT
STATE
HIDDEN AND FULL
PROGRAMMING MODE ACCESS
>0
PLOC
or
Not Active
Any State
After Parameter Display Loop with
correct code # at
COdE
prompt.
0
PLOC
Active
No Access
0
PLOC
or
Not Active
Not Active Access after Parameter Display Loop
COdE
dSP
0