METER UNIT ADDRESS
0
to
99
= RLC Protocol
1
to
247
= Modbus
Select a Unit Address that does not match an address number of
any other equipment on the serial link.
TRANSMIT DELAY
0.000
to
0.250
seconds
Following a transmit value (“*” terminator) or Modbus command,
the PAX2C will wait this minimum amount of time in seconds before
issuing a serial response.
The following programming steps are only available when Communications
Type(tYPE) is programmed for rLC.
ABBREVIATED PRINTING
NO
YES
Select NO for full print or Command T transmissions (meter
address, mnemonics and parameter data) or YES for abbreviated print
transmissions (parameter data only). This will affect all the parameters
selected in the print options. If the meter address is 00, the address
will not be sent during a full transmission.
PRINT OPTIONS
NO
YES
YES
- Enters the sub-menu to select the meter parameters to appear
during a print request. For each parameter in the sub-menu, select YES
for that parameter information to be sent during a print request or NO
for that parameter information not to be sent. A print request is
sometimes referred to as a block print because more than one
parameter information (meter address, mnemonics and parameter data) can be
sent to a printer or computer as a block.
DISPLAY
DESCRIPTION
FACTORY
SETTING
MNEMONIC
INPt
Signal Input
YES
INP
SP
*Setpoint
NO
SET
SPrr
Setpoint Ramp Rate
NO
RMP
OP
Output Power
NO
PWR
ProP
*Proportional Band
NO
PBD
Int
*Integral Time
NO
INT
dEr
*Derivative Time
NO
DER
ALr
Alarm Status (1-4)
NO
ALR
AL1
*Alarm Value 1
NO
AL1
AL2
*Alarm Value 2
NO
AL2
AL3
*Alarm Value 3
NO
AL3
AL4
*Alarm Value 4
NO
AL4
CtrL
Control Parameters
NO
CTL
* Active values
Addr
SRL
247
dLAY
SRL
0.010
SEC
Abrv
SRL
NO
OPt
SRL
NO