Device identification objects, Table 47, Hmt330 modbus device identification – Vaisala HMT330 User Manual
Page 207

Appendix C _________________________________________________________ Modbus Reference
VAISALA _______________________________________________________________________ 205
Code
Sub-Function Name
Notes
13 (0x0D)
Return Bus Exception Error
Count
Number of Modbus exception
responses sent
14 (0x0E)
Return Slave Message Count Number of Modbus messages
processed
15 (0x0F)
Return Slave No Response
Count
Number of Modbus messages
received without sending a
response. This happens for
received broadcast messages
(Modbus RTU only) or when
HMT330 is in the “Listen Only”
mode.
Although Modbus Diagnostics are standardized only for serial line
devices, HMT330 supports the same diagnostic functions also on
Modbus TCP.
NOTE
Resetting, powering up the transmitter, or reselecting the Modbus mode
(by serial command or with the user interface) resets all Modbus
diagnostic counters and cancels any “Listen Only” mode.
Device Identification Objects
HMT330 Modbus conforms to the extended identification level defined
in the Modbus Application Protocol Specification V1.1b. Both stream
access and individual access to the objects is supported.
Table 47
HMT330 Modbus Device Identification
Object Id
Object Name
Description
0x00
VendorName
“Vaisala”
0x01
ProductCode
Product code (e.g. “HMT330”)
0x02
MajorMinorVersion
Software version (e.g. “5.10”)
0x03
VendorUrl
“http://www.vaisala.com/”
0x04
ProductName
Product name of the instrument
0x80
SerialNumber
Serial number (e.g. “D0710040”)
0x81
CalibrationDate
Date of the last calibration
(e.g. “2011-02-07”, empty if not
available)
0x82
CalibrationText
Information text of the last calibration
(empty if not available)