Blower error conditions, Power supply error conditions – HP StorageWorks 2500 Disk System User Manual

Page 79

background image

From the back of the enclosure, power supply 01 is on the left, and power supply 02 is on the right.

ec is the error code.

The following sections define the power supply condition reports.

Table 22 Power supply error conditions

Error

condition

Severity

Description

Actions

0.2.en.01

Noncritical

AC input power is missing from the

power supply en.

1.

Verify that the power supply

AC power cord is properly

connected.

2.

Verify that the source circuit

breaker is on.

3.

If there is no AC power,

contact building facilities

management.

0.2.en.02

Unrecover-

able

Power supply is missing from location

en.
Enclosure shutdown is imminent.

Replace the power supply as

soon as possible.
A missing power supply

affects airflow and causes an

overheating condition. Even if

the power supply has failed,

leave it in the enclosure until a

replacement is available.

0.2.en.03

Critical

Unbalanced power supply load
A component in power supply en has

failed.

1.

Verify that the blower on the

power supply is functioning

properly. If not, replace the

blower.

2.

Replace the power supply

as soon as possible.

Blower error conditions

The format of a blower error condition report is 0.3.en.ec, where:

0.3. identifies a blower error.

en. identifies which blower is failing.
From the back of the enclosure, blower 01 is on the left, and blower 02 is on the right.

ec is the error code.

CAUTION:

A single blower operating at high speed can provide sufficient air flow to cool an enclosure and the

components for up to 100 hours. However, operating an enclosure at temperatures approaching

an overheating threshold can damage components. Immediate replacement of the defective blower

is required.