EMU temperature warning and shutdown operation

The EMU uses multiple temperature sensors to monitor enclosure conditions. A sensor is located in:

Each power supply

Each disk drive

The EMU

An algorithm involving data from multiple sensors determines the temperature in the enclosure. The

following occurs when an unacceptable temperature condition exists:

As the temperature approches a critical temperature condition, a noncritical alarm sounds to provide

time for corrective action before shutdown occurs.

If the temperature reaches a critical level, the EMU activates the alarm and starts a timer which

shuts down the enclosure in 7 minutes.