Proseries, Sonic-pro, Horizontal – Blue-White Sonic-Pro Hybrid Ultrasonic Flowmeters User Manual
Page 11: Determine the transducer mounting mode, Determine the 1st transducer location
Page 11
Sonic-Pro
Industries, Ltd.
Industries, Ltd.
ProSeries
by Blue-White Ind.
TM
NO
NO
Down flows
must have
back pressure
Pipe must be full
Air could be trapped
!
3
Determine the
transducer mounting mode
DOPPLER
All pipe types and sizes
When operated in the Doppler mode, the transducers
are always mounted directly opposite each other, 180
degrees around the pipe.
When operated in the Transit-Time mode, the front
faces of the transducers must face each other and be
positioned the correct distance apart. In V-mode, the
transducers are on the same side of the pipe. In Z-
mode, the transducers are on the opposite side of the
pipe, 180 degrees apart.
When factory configured, the appropriate Transit-
Time mounting mode is pre-configured and printed on
the serial label.
“V” Mount Mode
Typically smaller pipe
sizes from 2” to 6”
Separation
Distance
TRANSIT TIME
“Z” Mount Mode
Typically larger pipe
sizes from 4” to 100”
Separation
Distance
See section 6.2 for more information
Flow
or
Flow
Flow
or
Flow
Flow
or
Flow
TRANSDUCER MOUNTING LOCATION
NO
NO
Air bubbles may be present
OK
Sediment may be present
Horizontal
O
45
O
45
4
Determine the 1st
transducer location
The mounting surface must be
clean, smooth and free of
surface imperfections. Remove
all insulation material, loose
paint, etc. Clean the pipe
thoroughly. Use sandpaper if
necessary to remove surface
imperfections. Be sure to locate
the transducers on the side of
horizontal runs of pipe. Do not
mount the transducers over
weld seams. Place a mark
where the first transducer will
be located.
See section 6.5 for more information