beautypg.com

KROHNE BM 102 Handbook User Manual

Page 63

background image

BM

102

63

5

Technical data

5.1 Technical

data

Application

Range of applications

Continuous level measurement of liquids, pastes, slurries and
powders

Function and system design
Measuring principle

Time domain reflectometry

Equipment architecture

See section 5.2

Input

Measured variable

Distance (between the reference point – gauge flange facing –
and the product surface), level, liquid interface & volume

Measurement range

Variable according to probe type, see Equipment architecture,
section 5.2.1

Blocking Distance
(dead zone)

Variable according to probe type, see probe measurement limits,
see section 5.2.2

Output

Analogue

4 … 20 mA, passive output

Load

Passive outputs

750 ohms maximum

Error signal

22 mA

Temperature drift

25 ppm / K

Resolution

± 3 µA

Digital

HART®, passive output

Digital, Ex ia

HART®, passive intrinsically-safe output

Signal on alarm

Status markers via PC STAR 2 or HART® controller (HHC)

Performance characteristics
Accuracy

Level measurement

Liquids when probe length, L ≤ 15 m or 50 ft.

± 15 mm or 0.6 “ outside the dead zone
Optional: ± 5 mm or 0.2 “

Liquids when probe length, L > 15 m or 50 ft.

± 0.1% of the measured distance
Optional: ± 0.05% of the measured distance

Solids

(powders)

± 20 mm or 0.8 “

with 4 … 20 mA current output

± 0.01% of the measured distance

Reference operating conditions
Ambient temperature

+20°C ± 5°C or +68°F ± 9°F

Ambient air pressure

1013 mbar abs. ± 20 mbar or 14.69 psig ± 0.29 psi

Relative air humidity

60% ± 15%

Reference target

- coaxial probe :

water surface

- single probe :

Ø 0.8 m or Ø 31.5 in. metal plate

- twin probe :

metal block “short circuit”

Free space diameter

> 300 mm * or 11.81” *

Distance to obstruction

> 1 m or > 3.28 ft.


* not necessary for coaxial probe.