3.3.3 Quick
Configuration: configuration examples
The minimum functions (fct.) to be configured for a simple measurement are listed below:
Functions Definition
PCSTAR 2
HART
®
1.1.1
2.1.1.1
Tank Height
1.1.2 2.1.1.4 Dead
zone
1.3.1 … 4
2.1.3.1 … 4 Current
Output
1.7.0 2.1.7.0 Volume table*
*For volume measurements
Example procedures for each set of functions are given on the following pages. Each procedure is
given in a series of steps in table form and is according to the PCSTAR 2 F2-Configuration
parameter list. Please refer to section 3.3.4 for the equivalent parameters available on the HART
®
Communicator.
Definitions for quick configuration
* where PCSTAR 2 Fct. 1.3.1 (HART
®
Fct. 2.1.3.1) Current I1 Item is configured to “Level”
Typical gauge used for quick configuration examples:
Probe type:
twin Ø4 mm or 0.15 ” cable probe (type 4)
Product measured:
Water (dielectric constant,
εr = 80)
Tank height:
(PCSTAR 2: Fct. 1.1.1,
HART
®
: Fct. 2.1.1.1)
10000.00 mm or 33 ft.
Dead zone:
(PCSTAR 2: Fct. 1.1.2,
HART
®
: Fct. 2.1.1.4)
0.15 m or ½ ft. (see “probe measurement limits” in section 5.2.3
for the Ø4 mm or 0.15” twin cable probe, type 4)
Probe length, L
1
:
(PCSTAR 2: Fct. 1.1.6
HART
®
: Fct. 2.1.1.2)
9.00 m or 29.5 ft. (do not modify unless advised to)