KROHNE BM 102 Handbook User Manual

Page 28

background image

28

BM 102


Function

Input Range

Description

Enter 0.1 m or 3.9” …
probe length (max.:
24000 mm or 78¾ ft.)

1.1.6 Probe length

As per order

This value must be equal to the exact
length of the probe. This value should
be modified when the probe has been
replaced or shortened (cable probes).
The output unit is set via Fct. 1.2.4
Length Unit.
An automatic search for the probe tip
can be carried out when the tank is
empty to update the parameter using
the function F11 in the “Dynamic
Configuration” menu.
Probe length may be set greater than
tank height but less than 24 m or
78¾ ft. for special installations.