Installation and operating instructions BM 70 A/P

Page: 72

11/00

Annex A: Technical data

1

Range of application

Distance, level, volume and reflection measurement of liquids, pastes,
slurries, solids and particulate material on storage and process tanks or
containers made of metal or concrete, and also in stilling wells

2

Mode of operation / system structure

FMCW-Radar in the X-Band (8.5-9.9 GHz) with digital signal processing;
compact device, modular design

3

Input
Measured variable

Primary variables: distance, reflection; derived variables: level, volume

Measuring range

Min. tank height: 0.5 m
max. measuring range: 40 m (optionally upto 100m); Wave-Stick: 20 m,
BM 70 P = 35m

Block distance

Min. 0.2 to 1.0 m; see Sect. 3.3

Rate of change in level

10 m/min; BM 70 P

1m/min

4

Output
Variant 1
Ex-e current output HART

®

Type
Current range
Accuracy/linearity
Temperature drift
Load impedance

active (current source); Ex-e
4-20 mA (error: 2 mA or 22 mA)
0.05 % (rel. 20 mA; 25°C)

100 ppm/K (typically 30 ppm/K)

500

with switching output:
and digital input:

max. 100 mA / 30 V DC or 30 V AC; internal resistance

20

; potential-

free
to "freeze" the measured value; voltage: 5 to 28 V DC;
input resistance:

1 k

; potential-free

Variant 2
Ex-i current output HART

®

Type
Current range

Temperature drift
Accuracy/linearity
Supply voltage
Load impedance

passive (current sink); Ex-i
4-20 mA (error 3.6 or 22 mA);
4 mA constant for HART

®

-Multidrop

100 ppm/K (typically 30 ppm/K)

0.05 % (rel. 20 mA; 25°C)
8-30 V (terminals 31 and 32)

(U

S

- 8 V) / 22 mA, (U

S

= external supply

voltage)

with optional switching output:

6 ... 30 V; I

Low

2 V; I

High

900 µA (U = 30 V), I

High

= 200 µA (U = 8 V)

Variant 3
RS 485 interface

Transmission rate
Address:
Protocols:

1200 to 38400 bauds
0 to 255
KROHNE Protocol,
Modbus-RTU, HART

®

with additional current output

Type

Current range
Accuracy/linearity
Temperature drift
Load impedance
When operated as switching
output:

active (current source); not communicable;
Ex-e
4-20 mA (error 2 mA or 22 mA)
0.3 % (rel. 20 mA; 25°C)

200 ppm/K (typically 70 ppm/K)

250

Low: I < 2 mA; High: I = 22 mA
(R

250

) and no-load voltage

18 V

Variant 4: PROFIBUS-PA (Ex-i)
Hardware
Physical
Bus characteristics
Base current
Default current

to IEC 61 158-2 and the FISCO model
9 ... 30 V; 0.3 mA max.; 4.2 W max.
10 mA
6 mA

Variant 5: Foundation Fieldbus (FF)

see Supplementary Instructions

Breakdown signal

Current output: error signal 2/22 mA or 3.6 mA (Ex-i),
plain text in local display
Switching contact: opening or closing of the contact
Digital interfaces: error flags

5

Measuring accuracy
Error of measurement

Reference conditions and error curves: see Sect. 5.1 and 5.2

Repeatability

0.5 × error of measurement

Measured-value resolution

BM 70 A: 1 mm; BM 70 P: 0.1 mm

Effect of ambient temperature

No significant effect on measured value(- 1 ppm/°C);
(see also signal outputs)

6

Operating conditions

6.1

Installation conditions

Avoid interference reflections and multiple reflections

6.2

Ambient conditions
Hazardous locations

BM 70 A/P Ex:

Zone 0,1,2; IIC/IIB, T6...T2

Ambient temperature at signal converter

-20...+55°C

(

-24...+131°F)

Functional range:

-40...+70°C

(

-40...+158°F)

Flange temperature

Horn antenna, Wave-Guide

(Tamb

50°C/122°F):

-30...+130°C

(

-22...+266°F)