Page: 34

11/00

Ex-i Current output HART

®

with switching output:

Current output (non-communicable):

Current-
output

Switching output

max. 110mA/30V

41

42

32 31

+

-

-

+

+

unit

U max.= 30V

4-20mA

U min.

= 8V

Ex-i-supply

32 31

Current
output

- +

unassigned

-

+

4-20mA

max.250

RS 485 version:

PROFIBUS-PA or Foundation Fieldbus (FF)

B

B

A

A

RS 485

input

RS 485

output

32 31

Current
output

- +

-

+

4-20mA

max.250

32 31

Bus-

connection

PROFIBUS-PA / FF with current output:

PROFIBUS-PA / FF with switching output:

42

-

Ex-i-supply-

+

+

unit

+

U max.= 30V

current

output

4-20mA

U min.

= 8V

41

-

32 31

Bus-

connection

32 31

switching output

max. 110mA/30V

42 41

Bus-

connection

7.9 Terminating resistor for the RS 485 interface

A selector plug on the RS 485 board allows
optionally a high-resistance termination (presetting)
or a terminating resistor of 120

at the RS 485

connections A and B. For this purpose, the housing
(flameproof enclosure) of the BM 70 A/P signal con-
verter needs to be opened (see Sect. 9.3) and the
selector plug turned 180°, see sketch on the right.

120

RS485 signal-
output board

high-

impedance

....

....