8.2 Technical data: general information

INFORMATION!

The following data is provided for general applications. If you require data that is more
relevant to your specific application, please contact us or your local sales office.

Additional information (certificates, special tools, software,...) and complete product
documentation can be downloaded free of charge from the website (Download Center).

Basic

Advanced

Measuring system

Measuring principle

Bypass level indicator (principle of communicating tubes). A float in

the measuring chamber (Ø42 mm / 1.7¨) is magnetically-coupled to a

mechanical level indicator.

Application range

Level indication of liquids for

low-pressure applications and in

storage tanks

Level indication of liquids in

applications up to 40 barg /

580 psig

Measured value

Measured value

Measured value

Measured value

Primary measured value

Level of the float magnets in the measuring chamber

Secondary measured value

Level and volume of the liquid in the measuring chamber

Design

Options and variants

Options and variants

Options and variants

Options and variants

Variants

Lateral / lateral process connections

Axial / axial process connections

Top lateral / bottom axial process connections

Top axial / bottom lateral process connections

Options

Support bracket (a wall support for long bypass level indicators)

Analog transmitter without display (converter with 4...20 mA,

4...20 mA + HART®, PROFIBUS PA or FF output module mounted at

the top or bottom of the reed chain)

1

Analog transmitter with display (4...20 mA or 4...20 mA + HART®

converter mounted at the top or bottom of the reed chain)

1¼¨ threaded cover (for

installation/ removal of the float)

-

Anti-freeze cover for glass indicator tube (when the ambient

temperature is -40...-20°C / -40...-4°F)

-

OPTIFLEX 1300 C with Ø2 mm

single cable probe (if ½ BSPP top

axial connection is selected)

-

OPTIFLEX 1300 C (if DN40 PN40

top axial connection is selected )

-

OPTIWAVE 7300 C (if welded

antenna or DN40 PN40 top axial

connection is selected)

Accessories

Bistable limit switches (NAMUR or non-NAMUR)

Measuring range (ML)

0.3…5.3 m / 1…17.4 ft

0.3…5.3 m / 1…17.4 ft

(longer on request)