Operation – KROHNE BM 26 BASIC_ADVANCED EN User Manual
Page 39
OPERATION
6
39
BM 26 BASIC/ADVANCED
www.krohne.com
10/2012 - 4000347004 - HB BM26 Basic/Adv R04 en
Analog transmitter
Optional LCD indicator status:
OL
Current output is more than 22 mA
(more than 20 mA, if this option is
selected in the indicator). Overfill.
The level of the liquid is above the
maximum limit (if the indicator is
configured for level indication).
Lower the level of liquid below the
maximum limit.
Current output is more than 22 mA
(more than 20 mA, if this option is
selected in the indicator). The
analog transmitter has been
moved. A value more than 20 mA
no longer represents the
maximum limit.
Contact your local sales office for
advice.
Current output is more than 22 mA
(more than 20 mA, if this option is
selected in the indicator). The
analog transmitter is defective. A
value more than 20 mA no longer
represents the maximum limit.
Contact your local sales office for
advice.
Optional LCD indicator status:
-OL
Current output is less than 3.6 mA
(less than 4 mA, if this option is
selected in the indicator). The level
of the liquid is below the minimum
limit (if the indicator is configured
for level indication).
Increase the level of liquid until it is
above the minimum limit.
Current output is less than 3.6 mA
(less than 4 mA, if this option is
selected in the indicator). The
analog transmitter has been
moved. A value less than 4 mA no
longer represents the minimum
limit.
Contact your local sales office for
advice.
Current output is less than 3.6 mA
(less than 4 mA, if this option is
selected in the indicator). The
analog transmitter is defective. A
value less than 4 mA no longer
represents the minimum limit.
Contact your local sales office for
advice.
The level of the liquid is at or
above the maximum level, but
the analog transmitter output
doe not indicate that level has
reached its maximum limit
yet.
The density of the liquid is lower
than the value given in the
customer order data. The float is
too low in the liquid.
Make sure that the density of the
liquid is stable. Contact your local
sales office for advice.
The analog transmitter output
indicates that the liquid is at
or below the minimum level,
but the level of the liquid is
still above the minimum limit.
The density of the liquid is lower
than the value given in the
customer order data. The float is
too low in the liquid.
Make sure that the density of the
liquid is stable. Contact your local
sales office for advice.
The level of the liquid is below
the maximum level, but the
analog transmitter output
indicates that level has
already reached its maximum
limit.
The density of the liquid is higher
than the value given in the
customer order data. The float is
too high in the liquid.
Make sure that the density of the
liquid is stable. Contact your local
sales office for advice.
The analog transmitter output
is not yet at the minimum
level, but the level of the
liquid is at or below the
minimum limit.
The density of the liquid is higher
than the value given in the
customer order data. The float is
too high in the liquid.
Make sure that the density of the
liquid is stable. Contact your local
sales office for advice.
Error
Description
Corrective action