6.2.2 Error handling

Error

Description

Corrective action

Indicator column

Float failure

The red flaps at the bottom of the

indicator column are shown. The

float has sunk to the bottom of the

measuring chamber.

Make sure the measuring chamber

has not been completely drained.

Make sure the true density of the

liquid corresponds to the value

given in the order data. Contact

your local sales office to make sure

that the float is for the correct

density range.

If the float is damaged or corroded,

it is necessary to replace the float.

Order a new float from your local

sales office. Isolate the measuring

chamber and drain the liquid.

Remove the bottom plate flange

and the float. If your device is a

basic version, you will only be able

to remove the float if it has the

1¼ NPT connection at the bottom

of the measuring chamber

The level of the liquid is at or

above the maximum level, but

the indicator column doe not

indicate that level has

reached its maximum limit

yet.

The density of the liquid is lower

than the value given in the

customer order data. The float is

too low in the liquid.

Make sure that the density of the

liquid is stable. Contact your local

sales office for advice.

The indicator column

indicates that the liquid is at

or below the minimum level,

but the level of the liquid is

still above the minimum limit.

The density of the liquid is lower

than the value given in the

customer order data. The float is

immersed more than it should be.

Make sure that the density of the

liquid is stable. Contact your local

sales office for advice.

The level of the liquid is below

the maximum level, but the

indicator column indicates

that level has already reached

its maximum limit.

The density of the liquid is higher

than the value given in the

customer order data. The float is

not sufficiently immersed.

Make sure that the density of the

liquid is stable. Contact your local

sales office for advice.

The indicator column is not

yet at the minimum level, but

the level of the liquid is at or

below the minimum limit.

The density of the liquid is higher

than the value given in the

customer order data. The float is

immersed more than it should be.

Make sure that the density of the

liquid is stable. Contact your local

sales office for advice.