Installation, 5 level indicator column – KROHNE BM 26 BASIC_ADVANCED EN User Manual

Page 21

background image

INSTALLATION

3

21

BM 26 BASIC/ADVANCED

www.krohne.com

10/2012 - 4000347004 - HB BM26 Basic/Adv R04 en

Equipment needed:

• Magnet (supplied with the device)

How to make sure the column of rotating flaps is set to zero

• Hold the magnet in front of the glass tube at the bottom of the indicator column.

i

Make sure the red end of the magnet points at the glass tube.

• Move the magnet slowly up to the top the glass tube.

i

The flaps all turn to black. The indicator column is set to zero. You can now fill the tank.

3.5 Level indicator column

The level indicator column is attached to the measuring chamber before delivery. Customer
order data is used to calibrate its position. No other adjustment is necessary.

Figure 3-7: Set the indicator column to zero

1 Magnet - point the red end of the magnet at the glass tube

CAUTION!
Customer order data is used to calibrate the device. If liquid density changes, the device will not
measure correctly. Please contact our nearest sales office for advice.