Operation – KROHNE UFC 400 FOUNDATION FIELDBUS EN User Manual
Page 44
4
OPERATION
44
UFC 400
www.krohne.com
05/2013 - 4002813701 - AD FF UFC 400 R01 en
LIMITATION_MIN
LIMITATION_MIN
LIMITATION_MIN
LIMITATION_MIN
Lower Limit
R/W
Lower limitation of all flow values , before smoothing by time
constant, affects all outputs (Fct. C1.3.1).
-20.0 m/s
Settings:
-0.0010…-1000.0 m/s
LINEARIZATION
LINEARIZATION
LINEARIZATION
LINEARIZATION
Linearization
R/W
(Compensation for errors made at different Reynolds
Numbers (Fct. C1.7.1).
off
Settings:
off / on
LOW_FLOW_
LOW_FLOW_
LOW_FLOW_
LOW_FLOW_
CUTOFF
CUTOFF
CUTOFF
CUTOFF
Low flow cutoff
R/W
Sets the low flow cutoff (Fct. C1.3.4).
0.0 m/s
Settings:
0.0...100.0 m/s
METER_SIZE_
METER_SIZE_
METER_SIZE_
METER_SIZE_
FREE_VAL
FREE_VAL
FREE_VAL
FREE_VAL
Meter size
R/W
Sets the pipe diameter (Fct. C1.1).
100.0 mm
Settings:
25.0…3000.0 mm
METER_SIZE_
METER_SIZE_
METER_SIZE_
METER_SIZE_
TBL_VAL
TBL_VAL
TBL_VAL
TBL_VAL
Meter size
R/W
Sets the pipe diameter (Fct. C1.1).
100 mm
Settings:
250:25 mm (1 inch) / 320:32 mm (1.25 inch) / 400:40 mm (1.5
inch) / 500:50 mm (2 inch) / 650:65 mm (2.5 inch) / 800:80 mm
(3 inch) / 1000:100 mm (4 inch) / 1250:125 mm (5 inch) /
1500:150 mm (6 inch) / 2000:200 mm (8 inch) / 2500:250 mm
(10 inch) / 3000:300 mm (12 inch) / 3500:350 mm (14 inch) /
4000:400 mm (16 inch) / 4500:450 mm (18 inch) / 5000:500
mm (20 inch) / 5500:550 mm (22 inch) / 6000:600 mm (24
inch) / 6500:650 mm (26 inch) / 7000:700 mm (28 inch) /
7500:750 mm (30 inch) / 8000:800 mm (32 inch) / 8500:850
mm (34 inch) / 9000:900 mm (36 inch) / 9500:950 mm (38
inch) / 10000:1000 mm (40 inch) / 10500:1050 mm (42 inch) /
11000:1100 mm (44 inch) / 11500:1150 mm (46 inch) /
12000:1200 mm (48 inch) / 12500:1250 mm (50 inch) /
13000:1300 mm (52 inch) / 13500:1350 mm (54 inch) /
14000:1400 mm (56 inch) / 14500:1450 mm (58 inch) /
15000:1500 mm (60 inch) / 16000:1600 mm (64 inch) /
17000:1700 mm (68 inch) / 18000:1800 mm (72 inch) /
19000:1900 mm (76 inch) / 20000:2000 mm (80 inch) /
21000:2100 mm (84 inch) / 22000:2200 mm (88 inch) /
23000:2300 mm (92 inch) / 24000:2400 mm (96 inch) /
25000:2500 mm (100 inch) / 26000:2600 mm (104 inch) /
27000:2700 mm (108 inch) / 28000:2800 mm (112 inch) /
29000:2900 mm (116 inch) / 30000:3000 mm (120 inch)
NUM_PATHS
NUM_PATHS
NUM_PATHS
NUM_PATHS
Number of paths
R/W
Sets the number of active paths (Fct. D2.1).
3 paths
Settings:
1 path / 2 paths / 3 paths
PATH_LENGTH_1
PATH_LENGTH_1
PATH_LENGTH_1
PATH_LENGTH_1
Path length 1
R/W
Shows/Sets the length of path 1 (Fct. D2.3).
100 mm
Settings:
12.5…6000.0 mm
PATH_LENGTH_2
PATH_LENGTH_2
PATH_LENGTH_2
PATH_LENGTH_2
Path length 2
R/W
Shows/Sets the length of path 2 (Fct. D2.4).
100 mm
Settings:
12.5…6000.0 mm
PATH_LENGTH_3
PATH_LENGTH_3
PATH_LENGTH_3
PATH_LENGTH_3
Path length 3
R/W
Shows/Sets the length of path 3 (Fct. D2.5).
100 mm
Settings:
12.5…6000.0 mm
PING_TIME
PING_TIME
PING_TIME
PING_TIME
Ping time
R/W
Ping time (Fct. D1.11)
15.5 ms
Settings:
5.0…15.0 ms
Parameter
Parameter
Parameter
Parameter
DD name
Access
Description and settings
Initial Value