Operation – KROHNE UFC 400 FOUNDATION FIELDBUS EN User Manual
Page 28
4
OPERATION
28
UFC 400
www.krohne.com
05/2013 - 4002813701 - AD FF UFC 400 R01 en
SHED_RCAS
SHED_RCAS
SHED_RCAS
SHED_RCAS
Shed Remote Cascade
R/W
Time duration at which to give up on computer writes to
function block RCAS locations.
640000
Setting:
0...4294967295 in [1/32 ms]
SHED_ROUT
SHED_ROUT
SHED_ROUT
SHED_ROUT
Shed Remote Out
R/W
Time duration at which to give up on computer writes to
function block ROUT locations.
640000
Setting:
0...4294967295 in [1/32 ms]
TEST_RW
TEST_RW
TEST_RW
TEST_RW
Test R Write
Read/write test parameter - used only for conformance
testing.
Note: Subelements "1..15" have no function!
-
UPDATE_EVT
UPDATE_EVT
UPDATE_EVT
UPDATE_EVT
Update Event
This alert is generated by any change to the static data.
-
Unacknowledged
R/W
A discrete enumeration which is set to "Unacknowledged"
when an update occurs, and set to "Acknowledged" by a write
from a human interface device or other entity which can
acknowledge that the alarm/event has been noticed.
Uninitialized
Setting:
Uninitialized / Acknowledged / Unacknowledged
Update State
R
A discrete enumeration which gives an indication of whether
the alert has been reported.
Uninitialized
Setting:
Uninitialized / Reported / Not reported
Time Stamp
R
The time when evaluation of the block was started and a
change in alarm/event state was detected that is unreported.
The time stamp value will be maintained constant until alert
confirmation has been received - even if another change of
state occurs.
Uninitialized
Setting:
MM / DD / YY (Month / Day / Year)
HH:MM:SS (Hour:Minute:Second)
Static Revision
R
The static revision of the block whose static parameter was
changed and is being reported. It is possible for the present
value of static revision to be greater than this because static
can be changed at any time.
0
Setting:
0…65535
Relative Index
R
The OD index of the static parameter whose change caused
this alert, minus the FB starting index. If the update event was
caused by a write to multiple parameters at the same time,
then this attribute will be zero.
0
Setting:
0…65535
WRITE_ALM
WRITE_ALM
WRITE_ALM
WRITE_ALM
Write Alarm
Mix
This alert is generated if the write lock parameter is cleared.
-
Unacknowledged
R/W
A discrete enumeration which is set to "Unacknowledged"
when an alarm occurs, and set to "Acknowledged" by a write
from a human interface device or other entity which can
acknowledge that the alarm/event has been noticed.
Uninitialized
Setting:
Uninitialized / Acknowledged / Unacknowledged
Alarm State
R
A discrete enumeration which gives an indication of whether
the alert is active and whether it has been reported.
Uninitialized
Setting:
Uninitialized / Clear - reported / Clear - not reported / Active -
reported / Active - not reported
Parameter
Parameter
Parameter
Parameter
DD name
Access
Description and settings
Initial Value