Time Stamp

R

The time when evaluation of the block was started and a

change in alarm/event state was detected that is unreported.

The time stamp value will be maintained constant until alert

confirmation has been received - even if another change of

state occurs.

Uninitialized

Setting:

MM / DD / YY (Month / Day / Year)

HH:MM:SS (Hour:Minute:Second)

Subcode

R

An enumeration specifying the cause of the alert to be

reported.

-

Value

R

The value of the associated parameter at the time the alert

was detected.

-

FD_FAIL_MAP

FD_FAIL_MAP

FD_FAIL_MAP

FD_FAIL_MAP

Fail Map

R/W

This parameter enables or disables conditions to be detected

as active for this alarm category.

(28) (29) (30) (31)

Setting:

(00) Check / (01) Electronics : Operation Info /

(08) Electronics : Power Fail / (10) Configuration : Totaliser /

(11) Process : Signal Unreliable / (12) Process : Signal Lost /

(13) Process : Empty Pipe / (14) Electronics : IO Connection /

(15) Process : Current input / (16) M Process /

(17) M Configuration / (18) M Electronics / (19) M Sensor /

(20) S Process / (21) S Configuration / (22) S Electronics /

(23) S Sensor / (24) C Process / (25) C Configuration /

(26) C Electronics / (27) C Sensor / (28) F Process / (29) F

Configuration / (30) F Electronics / (31) F Sensor

FD_FAIL_MASK

FD_FAIL_MASK

FD_FAIL_MASK

FD_FAIL_MASK

Fail Mask

R/W

This parameter allows the user to suppress any single or

multiple conditions that are active, in this category, from

being broadcast to the host through the alarm parameter.

(28) (29) (30) (31)

Setting:

(00) Check / (01) Electronics : Operation Info / (08) Electronics

: Power Fail / (10) Configuration : Totaliser / (11) Process :

Signal Unreliable / (12) Process : Signal Lost / (13) Process :

Empty Pipe / (14) Electronics : IO Connection / (15) Process :

Current input / (16) M Process / (17) M Configuration / (18) M

Electronics / (19) M Sensor / (20) S Process / (21) S

Configuration / (22) S Electronics / (23) S Sensor / (24) C

Process / (25) C Configuration / (26) C Electronics / (27) C

Sensor / (28) F Process / (29) F Configuration / (30) F

Electronics / (31) F Sensor

FD_FAILK_PRI

FD_FAILK_PRI

FD_FAILK_PRI

FD_FAILK_PRI

Fail Priority

R/W

This parameter allows the user to specify the priority of this

alarm category.

0

Setting:

0...15

FD_EXTENDED_

FD_EXTENDED_

FD_EXTENDED_

FD_EXTENDED_

ACTIVE_1

ACTIVE_1

ACTIVE_1

ACTIVE_1

FD_EXTENDED_

ACTIVE_1

R

An optional parameter to allow the user finer detail on

conditions causing an active condition in the FD_*_ACTIVE

parameter.

Uninitialized

Setting:

(00) Optical Interf. Active / (01) Disp. 2 Overrange / (02) Disp. 1

Overrange / (06) RB is set to OOS / (07) Fieldbus No

Connection / (11) Status Out B Active / (13) Status Out A

Active / (14) Control In B Active / (15) Control In A Active / (30)

Sensor Starting up / (31) Zero Calibr. Running

FD_EXTENDED_

FD_EXTENDED_

FD_EXTENDED_

FD_EXTENDED_

ACTIVE_2

ACTIVE_2

ACTIVE_2

ACTIVE_2

FD_EXTENDED_

ACTIVE_2

R

An optional parameter to allow the user finer detail on

conditions causing an active condition in the FD_*_ACTIVE

parameter.

Uninitialized

Setting:

(20) Disp. 2 no measure values / (21) Dsp. 1 no measure

values / (28) IO B No Value for Binary Output / (29) IO B No

Value for Current Output / (30) IO A No Value for Binary

Output / (31) IO A No Value for Current Output

Parameter

Parameter

Parameter

Parameter
DD name

Access

Description and settings

Initial Value