beautypg.com

Operation – KROHNE UFC 400 FOUNDATION FIELDBUS EN User Manual

Page 32

background image

4

OPERATION

32

UFC 400

www.krohne.com

05/2013 - 4002813701 - AD FF UFC 400 R01 en

ACTUAL

Actual

R

This is the current mode of the block, which may differ from

the target based on operating conditions. Its value is

calculated as part of block execution.

OOS

Setting:

Auto / Manual / OOS

PERMITTED

Permitted

R/W

Defines the modes which are allowed for an instance in the

block. The permitted mode is configured based on application

requirements.

Auto

OOS

Setting:

Auto / Manual / OOS

NORMAL

Normal

R/W

This is the mode which the block should be set to during

normal operating conditions.

Auto

Setting:

Auto / Manual / OOS

ST_REV

ST_REV

ST_REV

ST_REV

Static Revision

R

The revision level of the static data associated with the

function block. The revision value will be incremented each

time a static parameter value in the block is changed.

0

Setting:

0...65535

STRATEGY

STRATEGY

STRATEGY

STRATEGY

Strategy

R/W

The strategy field can be used to identify grouping of blocks.

This data is not checked or processed by the block.

0

Setting:

0...65535

TAG_DESC

TAG_DESC

TAG_DESC

TAG_DESC

Tag Description

R/W

This is the user description of the intended application of the

block.

blanks

Setting:

≤32 digits

ACK_OPTION

ACK_OPTION

ACK_OPTION

ACK_OPTION

Acknowledge

Option

R/W

Selection of whether alarms associated with the function

block will be automatically acknowledged.

Uninitialized

Setting:

HiHi Alm Auto Ack / Hi Alm Auto Ack / LoLo Alm Auto Ack / Lo

Alm Auto Ack / Blk Alm Auto Ack / Fail Alm Auto Ack / Off

Spec Alm Auto Ack / Maint Alm Auto Ack / Check Alm Auto

Ack

ALARM_HYS

ALARM_HYS

ALARM_HYS

ALARM_HYS

Alarm Hysteresis

R/W

Amount the PV must return within the alarm limits before the

alarm condition clears. Alarm hysteresis is expressed as a

percent of the PV span.

0.5

Setting:

0...50%

ALARM_SUM

ALARM_SUM

ALARM_SUM

ALARM_SUM

Alarm Summary

Mix

The current alert status, unacknowledged states, unreported

states and disabled states of the alarms associated with the

function block.

-

Current

R

The active status of each alarm.

Uninitialized

Setting:

HiHi Alarm / Hi Alarm / LoLo Alarm / Lo Alarm / Block Alarm

Unacknowledged

R

The unacknowledged state of each alarm.

Uninitialized

Setting:

HiHi Alarm Unack / Hi Alarm Unack / LoLo Alarm Unack / Lo

Alarm Unack / Block Alarm Unack

Unreported

R

The unreported states of each alarm.

Uninitialized

Setting:

HiHi Alarm Unrep / Hi Alarm Unrep / LoLo Alarm Unrep / Lo

Alarm Unrep / Block Alarm Unrep

Parameter

Parameter

Parameter

Parameter
DD name

Access

Description and settings

Initial Value