Operation – KROHNE UFC 400 FOUNDATION FIELDBUS EN User Manual
Page 30
4
OPERATION
30
UFC 400
www.krohne.com
05/2013 - 4002813701 - AD FF UFC 400 R01 en
FORMAT_2P_2L
FORMAT_2P_2L
FORMAT_2P_2L
FORMAT_2P_2L
Form. 2.Page 2.Line
R/W
No. of decimal places for 2st line of 2nd page (Fct. C5.4.4).
X.X
Setting:
#X. / #X.X / #X.XX / #X.XXX / #X.XXXX / #X.XXXXX /
#X.XXXXXX / #X.XXXXXXX / #X.XXXXXXXX / automatic
FORMAT_2P_3L
FORMAT_2P_3L
FORMAT_2P_3L
FORMAT_2P_3L
Form. 2.Page 3.Line
R/W
No. of decimal places for 3st line of 2nd page (Fct. C5.4.5).
X.X
Setting:
#X. / #X.X / #X.XX / #X.XXX / #X.XXXX / #X.XXXXX /
#X.XXXXXX / #X.XXXXXXX / #X.XXXXXXXX / automatic
IO_CONNECTION
IO_CONNECTION
IO_CONNECTION
IO_CONNECTION
Status IO Connection
R/W
Defines the influence of the diagnostic ''Electronic : IO
Connection'' (FD_xx_14) to the TB measurements status (Fct.
C1.10.7).
Information
Setting:
Information / Maintenance Required / Checks in progress /
Out Of Specification / Failure
PASSWRD
PASSWRD
PASSWRD
PASSWRD
Password
R/W
Password to activate access rights to restricted parameters.
0
POWER_FAILURE
POWER_FAILURE
POWER_FAILURE
POWER_FAILURE
Status Power Failure
R/W
Defines the influence of the diagnostic ''Electronic : Power
Failure'' (FD_xx_8) to the TB measurements status (Fct.
C1.10.8).
Information
Setting:
Information / Maintenance Required / Checks in progress /
Out Of Specification / Failure
PROTECT_INFO
PROTECT_INFO
PROTECT_INFO
PROTECT_INFO
Access protection
R
Current protection level to restricted parameters.
Production
Setting:
Concentration / bit 5…6: not use / User / Service level /
Production / Custody Transfer / Write Lock
SERIAL_NUMBER
SERIAL_NUMBER
SERIAL_NUMBER
SERIAL_NUMBER
Serial Number
R
Device serial number, serial number of the system.
Current serial
number
SIGNAL_LOST
SIGNAL_LOST
SIGNAL_LOST
SIGNAL_LOST
Status Signal Lost
R/W
Defines the influence of the diagnostic ''Process : Signal
Lost'' (FD_xx_12) to the TB measurements status (Fct.
C1.10.4).
Information
Setting:
Information / Maintenance Required / Checks in progress /
Out Of Specification / Failure
SIGNAL_UNRELIABLE
SIGNAL_UNRELIABLE
SIGNAL_UNRELIABLE
SIGNAL_UNRELIABLE
Status Signal
Unreliable
R/W
Defines the influence of the diagnostic ''Process : Signal
Unreliable'' (FD_xx_11) to the TB measurements status (Fct.
C1.10.5).
Information
Setting:
Information / Maintenance Required / Checks in progress /
Out Of Specification / Failure
SW_SIMULATE
SW_SIMULATE
SW_SIMULATE
SW_SIMULATE
SW simulate
R/W
Enable/disable simulation like simulate Hardware jumper.
Disable
Setting:
Disable / Active
Variable_2P_1L
Variable_2P_1L
Variable_2P_1L
Variable_2P_1L
Disp. 2.Page 1.Line
R/W
Select the Function Block output value to display at 2nd page
1st line (Fct. C5.4.1).
AI1
Setting:
AI10 / AI2 / AI3 / AI4 / PID / IT1 / IT2
Variable_2P_2L
Variable_2P_2L
Variable_2P_2L
Variable_2P_2L
Disp. 2.Page 2.Line
R/W
Select the Function Block output value to display at 2nd page
2nd line (Fct. C5.4.3).
AI1
Setting:
AI10 / AI2 / AI3 / AI4 / PID / IT1 / IT2
Parameter
Parameter
Parameter
Parameter
DD name
Access
Description and settings
Initial Value