beautypg.com

Operation – KROHNE UFC 400 FOUNDATION FIELDBUS EN User Manual

Page 22

background image

4

OPERATION

22

UFC 400

www.krohne.com

05/2013 - 4002813701 - AD FF UFC 400 R01 en

Unacknowledged

R/W

A discrete enumeration which is set to "Unacknowledged"

when an alarm occurs, and set to "Acknowledged" by a write

from a human interface device or other entity which can

acknowledge that the alarm/event has been noticed.

Uninitialized

Setting:

Uninitialized / Acknowledged / Unacknowledged

Alarm State

R

A discrete enumeration which gives an indication of whether

the alert is active and whether it has been reported.

Uninitialized

Setting:

Uninitialized / Clear - reported / Clear - not reported / Active -

reported / Active - not reported

Time Stamp

R

The time when evaluation of the block was started and a

change in alarm/event state was detected that is unreported.

The time stamp value will be maintained constant until alert

confirmation has been received - even if another change of

state occurs.

Uninitialized

Setting:

MM / DD / YY (Month / Day / Year)

HH:MM:SS (Hour:Minute:Second)

Subcode

R

An enumeration specifying the cause of the alert to be

reported.

-

Value

R

The value of the associated parameter at the time the alert

was detected.

-

FD_MAINT_MAP

FD_MAINT_MAP

FD_MAINT_MAP

FD_MAINT_MAP

Maintenance Map

R/W

This parameter enables or disables conditions to be detected

as active for this alarm category.

(16) (17) (18) (19)

Setting:

(00) Check / (01) Electronics : Operation Info /

(08) Electronics : Power Fail / (10) Configuration : Totaliser /

(11) Process : Signal Unreliable / (12) Process : Signal Lost /

(13) Process : Empty Pipe / (14) Electronics : IO Connection /

(15) Process : Current input / (16) M Process /

(17) M Configuration / (18) M Electronics / (19) M Sensor /

(20) S Process / (21) S Configuration / (22) S Electronics /

(23) S Sensor / (24) C Process / (25) C Configuration /

(26) C Electronics / (27) C Sensor / (28) F Process / (29) F

Configuration / (30) F Electronics / (31) F Sensor

FD_MAINT_MASK

FD_MAINT_MASK

FD_MAINT_MASK

FD_MAINT_MASK

Maintenance Mask

R/W

This parameter allows the user to suppress any single or

multiple conditions that are active, in this category, from

being broadcast to the host through the alarm parameter.

Setting:

(00) Check / (01) Electronics : Operation Info /

(08) Electronics : Power Fail / (10) Configuration : Totaliser /

(11) Process : Signal Unreliable / (12) Process : Signal Lost /

(13) Process : Empty Pipe / (14) Electronics : IO Connection /

(15) Process : Current input / (16) M Process /

(17) M Configuration / (18) M Electronics / (19) M Sensor /

(20) S Process / (21) S Configuration / (22) S Electronics /

(23) S Sensor / (24) C Process / (25) C Configuration /

(26) C Electronics / (27) C Sensor / (28) F Process / (29) F

Configuration / (30) F Electronics / (31) F Sensor

FD_MAINT_PRI

FD_MAINT_PRI

FD_MAINT_PRI

FD_MAINT_PRI

Maintenance Priority

R/W

This parameter allows the user to specify the priority of this

alarm category.

0

Setting:

0...15

Parameter

Parameter

Parameter

Parameter
DD name

Access

Description and settings

Initial Value