Operation – KROHNE UFC 400 FOUNDATION FIELDBUS EN User Manual
Page 27
OPERATION
4
27
UFC 400
www.krohne.com
05/2013 - 4002813701 - AD FF UFC 400 R01 en
GRANT_DENY
GRANT_DENY
GRANT_DENY
GRANT_DENY
Grant Deny
R/W
Options for controlling access of host computers and local
control panels to operating, tuning and alarm parameters of
the block.
-
GRANT
Grant
R/W
Depending on the philosophy of the plant, the operator or a
higher level device (HLD) or a local operator's panel (LOP) in
the case of "Local", may turn on an item of the "Grant"
attribute - "Program, Tune, Alarm or Local".
Uninitialized
Setting:
Program / Tune / Alarm / Local / Operate
DENY
Deny
R/W
The Denied attribute is limited for use by a monitoring
application in an interface device and may not be changed by
an operator.
Uninitialized
Setting:
Program denied / Tune denied / Alarm denied / Local denied /
Operate denied
HARD_TYPES
HARD_TYPES
HARD_TYPES
HARD_TYPES
Hardware Types
R
The types of hardware available as channel numbers.
Scalar input
ITK_VER
ITK_VER
ITK_VER
ITK_VER
ITK Version
(Interoperatibility Test
Kit)
R
Major revision number of the interoperability test case used to
register this device.
5
LIM_NOTIFY
LIM_NOTIFY
LIM_NOTIFY
LIM_NOTIFY
Limit Notify
R/W
Maximum number of unconfirmed alert notify messages
allowed.
20
Setting:
0...255
MANUFAC_ID
MANUFAC_ID
MANUFAC_ID
MANUFAC_ID
Manufacturer ID
R
Manufacturer identification number - used by an interface
device to locate the DD file for the resource.
KROHNE
Setting:
KROHNE
MAX_NOTIFY
MAX_NOTIFY
MAX_NOTIFY
MAX_NOTIFY
Maximum Notify
R
Maximum number of unconfirmed alert notify messages
possible.
20
Setting:
0...255
MEMORY_SIZE
MEMORY_SIZE
MEMORY_SIZE
MEMORY_SIZE
Memory Size
R
Available configuration memory in the empty resource. To be
checked before attempting a download.
0
MIN_CYCLE_T
MIN_CYCLE_T
MIN_CYCLE_T
MIN_CYCLE_T
Minimium Cycle Time
R
Time duration of the shortest cycle interval of which the
resource is capable (in [1/32 ms]).
6400
NV_CYCLE_T
NV_CYCLE_T
NV_CYCLE_T
NV_CYCLE_T
Nonvolatile Cycle
Time
R
Interval between writing copies of NV parameters to non-
volatile memory. Zero means never (in [1/32 ms]).
256000
RESTART
RESTART
RESTART
RESTART
Restart
R/W
Allows a manual restart to be initiated. Several degrees of
restart are possible. They are 1: Run, 2: Restart resource, 3:
Restart with defaults and 4: Restart processor.
Run
Setting:
Uninitialized / Run / Resource / Defaults / Processor
RS_STATE
RS_STATE
RS_STATE
RS_STATE
Resource State
R
State of the function block application state machine.
Standby
Setting:
Uninitialized / Start_Restart / Initialization / Online Linking /
Online / Standby / Failure
SET_FSTATE
SET_FSTATE
SET_FSTATE
SET_FSTATE
Set Fault State
R/W
Allows the fault state condition to be manually initiated by
selecting "Set".
Off
Setting:
Off
Parameter
Parameter
Parameter
Parameter
DD name
Access
Description and settings
Initial Value