beautypg.com

List of warnings and cautions – KEPCO BOP 1KW-MG Operator Manual, Firmware Ver.4.12 and higher User Manual

Page 7

background image

LIST OF

WARNINGS AND CAUTIONS

BOP 1KW OPR 3/10/14

E

PAGE

WARNING/CAUTION

3-20

WARNING:

For inductive loads, and especially superconducting magnet type loads,

the inherent offset of the BOP in the OFF state may generate significant

current in the circuit. A properly rated switch in parallel with a resistor

must be connected between the power supply and the load. The switch

must be open and the BOP front panel LCD must read 0V, 0A before re-

moving or installing connections between BOP and load.

3-20

WARNING:

For both inductive loads and constant-current-type active electronic

loads when the BOP output is set to OFF, a path is provided for absorbing

either the energy accumulated in the reactance of the load during the ON

state, or energy delivered by an electronic load. This prevents damage to

the load and power supply as well as providing safety for the user. How-

ever, In addition to the built-in safety features, constant-current-type ac-

tive electronic loads must be adjusted to zero and the BOP front panel

LCD must read 0V, minimum current, before handling the power supply-

to-load connections.

3-21

WARNING:

Accessing the BOP after the output is disabled in BATTERY mode is haz-

ardous because (1) high current arcing is possible and (2) either the ex-

ternal battery voltage, or the voltage (±Voltage Protection max) on the

BOP output terminals may be dangerous. Therefore, for battery and con-

stant-voltage-type active electronic loads it is recommended that two

properly rated external switches be installed for safety: one in series with

the battery, and one across the BOP output. After the unit is set to OFF,

first open the switch in series with the battery, then close the switch

across the BOP output to ensure safety before handling BOP connec-

tions. When connecting the battery, the switch across the output should

be opened after the connections are complete and then the switch in se-

ries with the battery should be closed. If the constant-voltage-type active

electronic load is adjusted to zero before handling the power supply-to-

load connections, only the switch across the BOP output is required.

3-30

WARNING:

Be sure that output power is OFF (Standby indicator lit) while connecting

monitoring device. Be sure that connections are secure and that termi-

nals are not inadvertently shorted.

3-35

WARNING:

Dangerous voltages are present at the output terminals: Do not touch!

Disconnect load before running this test.

4-8

WARNING:

The sense resistor will be dissipating full rated current of the BOP. If it is

hot to the touch, the sense resistor value, power rating and/or cooling are

incorrect; refer to PAR. 4.3 and Table 4-2.

4-14

WARNING:

The sense resistor will be dissipating full rated current of the BOP. If it is

hot to the touch, the sense resistor value, power rating and/or cooling are

incorrect; refer to PAR. 4.4 and Table 4-2.