2 operational status register, Operational status register -66 – KEPCO BOP 1KW-MG Operator Manual, Firmware Ver.4.12 and higher User Manual
Page 132
3-66
BOP HIPWR 031014
3.6.7.2
OPERATIONAL STATUS REGISTER
The OPERational condition register contains conditions which are a part of the instrument’s nor-
mal operation. The definition of each of these bits (condition register) is as follows:
• 0 through 4 - Not Used — always zero.
• 5 - Waiting for Trigger — 1 indicates the trigger system is enabled. If trigger source is
external and the trigger input goes low, the WTG will remain in a one condition until
after the trigger input goes high.
• 6 - Transient Armed — 1 indicates the transient function is enabled,
• 7 - Not Used — always zero.
• 8 - Constant Voltage — 1 indicates the instrument is in constant voltage mode.
• 9 - Transient Complete — 1 indicates transient has been completed. Not readable in
OPERation Status Condition register.
• 10 - Constant Current — 1 indicates the instrument is in constant current mode.
• 11 - Sample Complete — 1 indicates the sample has been completed.
• 12 - List Complete — 1 indicates the programmed list has been completed. Not readable
in OPERation Status Condition register.
• 13 - Not Used — always zero.
• 14 - List Running — 1 indicates the programmed list is in progress.
• 15 - Not Used — always zero.