beautypg.com

6 load connection using local sensing, 7 load connection using remote sensing, 6 cooling – KEPCO BOP 1KW-MG Operator Manual, Firmware Ver.4.12 and higher User Manual

Page 50: 7 setting up the unit, 1 consider the load type, Caution, Load connection using local sensing -12, Load connection using remote sensing -12, Cooling -12, Setting up the unit -12

background image

2-12

BOP HIPWR 031014

NOTE

REGARDLESS OF OUTPUT CONFIGURATION, EITHER LOCAL OR REMOTE OUT-
PUT SENSE LINES MUST BE CONNECTED FOR OPERATION.

1. OBSERVE POLARITIES: The OUT S sensing wire must be connected to the OUT-
PUT
load wire, and the COM S sensing wire must be connected to the COMMON load
wire.

2. IF LOCAL SENSING IS USED, INSTALL LINKS (see Figure 2-3).

CAUTION: The safety features incorporated into the BOP to handle energy from Active

loads are unable to protect the power supply or the load if input power to the
BOP is lost or if the BOP malfunctions. It is recommended that the user mon-
itor “Power OK” flag pins 3 and 4 of the external Protect Port (see Table 2-4)
and implement a fast-acting means of disconnecting capacitive loads or
crowbarring inductive loads to prevent damage to both the BOP and the load
in the event of input power loss.

2.5.6

LOAD CONNECTION USING LOCAL SENSING

Figure 2-3 shows a typical configuration using local sensing and a grounded load; for local
sensing with an isolated (“floating”) load, do not install the ground connection (see Figure 2-3,
Note 2).

2.5.7

LOAD CONNECTION USING REMOTE SENSING

Figure 2-4 shows a typical configuration using remote sensing and a grounded load; for remote
sensing with an isolated (“floating”) load, do not install the ground connection (see Figure. 2-4,
Note 2).

Use #22 AWG wire, twisted pair for remote sense connections.

2.6

COOLING

The power devices used within the power supply are maintained within their operating tempera-
ture range by means of internal heat sink assemblies and by two cooling fans. Periodic cleaning
of the power supply interior is recommended. If the power supply is located within a confined
space, take care that the ambient temperature, which is the temperature of the air immediately
surrounding the power supply, does not rise above the specified limits (see Table 1-2).

2.7

SETTING UP THE UNIT

The following paragraphs describe the connections and initial BOP setup needed to operate in
the desired mode.

2.7.1

CONSIDER THE LOAD TYPE

The BOP can be configured to respond differently to the Output OFF command, depending on
whether the load is defined as Active, Resistive or Battery. Refer to PAR. 3.3.6 to configure this
setting.