Watlow Silver Series User Manual
Page 75
Using EZware-5000
67
Action modes include Bit ON, Bit OFF, or Word write.
Bit ON: Start action sets the Action address bit. End action clears the Action address bit.
Bit OFF: Start action clears the Action address bit. End action sets the Action address bit.
Word write value settings – Constant: Start action writes the Start value into the Action address register. End action
writes the End value into the Action address register.
Word write value settings – Address: Start action writes the value stored in the designated register into the Action
address register. End action writes the value stored in the designated register+1 into the Action address register.
Note: The end action is only available when Enable termination action is checked on the Time Set tab.
Click the Time Set tab to configure the start and end times for the scheduled action. When Constant is selected, the
action is configured to occur on the specified days at the specified times. Multiple days can be selected. If the start
and end times need to span several days, select the Setting on individual day checkbox.
When Address is selected, the start and end times are determined by values in 11 consecutive registers beginning
with the designated Time setting address as follows:
Address
Function
Details
Time setting address
Control
Set to 1 to load the Scheduler with
the current time data. Do this each
time the start and end times are
updated in the registers.
Time setting address + 1
Status
Bit 0 is set when the time data has
been properly loaded.
Bit 1 is set when there has been an
error in loading the time data.
Time setting address + 2
Action mode
Set Bit 0 to use end time.
Clear Bit 0 and the Scheduler will not
use end time.
Time setting address + 3
Start time (day)
Bits 0-6 determine day of the week
the Start Action is executed.
Bit 0=Sunday; Bit 6=Saturday.
Time setting address + 4
Start time (hour)
This register determines the hour the
Start Action is executed.
Range is 0-23.
Time setting address + 5
Start time (minute)
This register determines the minute
the Start Action is executed.
Range is 0-59.
Time setting address + 6
Start time (second)
This register determines the second
the Start Action is executed.
Range is 0-59.
Time setting address + 7
End time (day)
Bits 0-6 determine day of the week
the End Action is executed.
Bit 0=Sunday; Bit 6=Saturday.
Note: If bit 0 of the Action Mode
register is clear, the Scheduler will
not execute the End Time action.
1010-1007, Rev. 10