Using EZware-5000

93

To configure Security tab settings:

The Security tab is used to set up a table of users, user levels (access classes), and passwords. Up to 12 users can be

individually enabled, and each has a unique password and combination of any six access classes (A-F). Only numbers

are allowed for password.

When an object is created, it can be assigned an access class (A-F). When that object is activated (for example, a

button is touched), the HMI compares the access classes allowed for the currently logged-in user to the access class

specified for the object. If the access class of the object is within the classes allowed, the object’s action is executed.

The access class for an object is configured in the User restriction section of the Security tab for that object. So, for

example, if you wish to set the access class for a set bit object, click on the Security tab of that object’s properties

dialog, as shown below:

1010-1007, Rev. 10