beautypg.com

Watlow Silver Series User Manual

Page 70

background image

62

EZware5000 Series Programming Manual

Line: The data is plotted as a Line graph, with squares plotted at each data point.

Point: The data is plotted as squares at each data point.

X-axis projection: The data is plotted as a line graph (no squares). The plot is filled along the X-axis.

Y-axis projection: The data is plotted as a line graph (no squares) with the X and Y data transposed. The plot is filled

along the Y-axis.

The Reference line section lets you configure up to four horizontal lines that can be drawn across the plot. Each line

can be enabled separately, and can have a unique color and position. The position specified for each line is relative to

the values entered in the Low Limit and High Limit fields. If the Limit from PLC box is checked, the reference lines are

referenced to the values entered in the specified register addresses (low limit = value in register address; high limit =

value in register address + 1).

Alarm Bar

The Alarm Bar Object is used to display alarms detected by the Alarm (Event) Log Object. It displays the alarm

message for each current alarm in a single horizontal scrolling line across the Alarm Bar’s display. Only the most

recent alarm appears in the Alarm Bar.

Alarm Display

The Alarm Display Object is used to display alarms detected by the Alarm (Event) Log Object. It displays the alarm

message for each alarm in a table format arranged in chronological order. All current alarms are displayed in the

Alarm Display and are removed from the list once the alarm condition is cleared.

An Alarm Acknowledge function can be enabled, which provides a Write address for the Alarm Display. Each

alarm/event can be acknowledged by touching the message in the Alarm Display. A different color can be assigned for

the Acknowledge status.

An Indirect Window can be configured to popup when the alarm/event is acknowledged to provide additional

information to the operator on how to proceed. The Indirect Window should be placed on the same window as the

Alarm Display. The window number is configured in the Alarm (Event) Log’s Message tab (Write value for Event

Display object) and is written into the Write address assigned in the Event Display.

Event Display

The Event Display Object is used to display alarms or events monitored by the Alarm (Event) Log Object. Events can be

displayed in Real-time or History mode. In Real-time mode, each alarm/event can be acknowledged by touching the

alarm/event in the Event Display. Different colors can be assigned for the Acknowledge and Return To Normal

statuses.

An Indirect Window can be configured to popup when the alarm/event is acknowledged to provide additional

information to the operator on how to proceed. The Indirect Window should be placed on the same window as the

Event Display. The window number is configured in the Alarm (Event) Log’s Message tab (Write value for Event

Display object) and is written into the Write address assigned in the Event Display.

In History mode, alarm/events from previous days can be displayed. The Write address changes to History Control

address, and the value in the History Control register determines which historical data is displayed. When the value in

the History Control register is 0, the data for today is displayed in the Event Display. When the value is 1, the data

from yesterday is displayed, when the value is 2, the data from two days ago is displayed, etc. Use the Option List

configured for “Source of item data: Dates of historical data” to select the day by date.

Check Enable reading multiple histories to display events from more than one day at a time. There are two modes:

With Number of days selected, the value entered in the History control register determines the starting day (most

recent, where 0 = today) and the value in the History control register + 1 determines the number of days of data

1010-1007, Rev. 10