2. Installation Requirements
•
Decide on the thickness of the enclosure wall, based on the level of
strength required: For details, read chapter 3, "Panel Cut Dimensions"
(see page 20).
•
Even if panel thickness is within recommended range for “Panel Cut
Dimensions”, the panel could warp, depending on panel’s material, size,
and installation location of GP unit or other devices. To prevent panel
warpage, the installation surface may need to be strengthened.
•
Check that the installation panel or cabinet's surface is flat, in good
condition and has no jagged edges.
•
Be sure that the surrounding air temperature and the ambient humidity are
within their designated ranges. Surrounding air temperature:
0 to 55 °C (32 to 131 °F)
ambient humidity: 10 to 90%RH; wet bulb temperature: maximum 39 °C (102 °F).
When installing the GP unit in a cabinet or enclosure, the surrounding air
temperature is the cabinet’s or enclosure’s internal temperature.
•
Be sure that heat from surrounding equipment does not cause the GP unit
to exceed its standard operating temperature.
•
When installing the GP unit vertically, install the GP unit so that the power
supply connector on the rear surface of the unit is at the top.
(1) Power Connector
Panel
Face
Cabinet
Interior
(1)
- GP4500R - 10.4 Standard HMIs with Rear Mounting Options" GP4400R - 7.5 Standard HMI with Rear Mounting Options" GP4300R - 5.7 Standard HMI with Rear Mount" GP4300M - 5.7 Modular HMI" GP4200M - 3.5 Modular HMI" GP4500 - 10.4 W Model HMI" GP4400 - 7.0 W Model HMI" GP4300 - 5.7 W Model HMI" GP4200 - 3.5 W Model HMI" GP4600 - 12.1 Standard HMIs" GP4500 - 10.4 Standard HMIs" GP4400 - 7.5 Standard HMI" GP4300 - 5.7 Standard HMI" GP4200 - 3.5 Standard HMIs"