Parameter menu (m2), Parameter menu, Ttings (chapter 7.3.2), reference – TREND NX Variable Speed Drives User Manual
Page 90: See chapter 7.3.2
CONTROL KEYPAD
vacon • 73
24-hour support +358 (0)40 837 1150 • Email: [email protected]
7
7.3.2 Parameter
menu
(M2)
Parameters are the way of conveying the commands of the user to the frequency converter. The parameter
values can be edited by entering the
Parameter Menu
from the
Main Menu
when the location indication M2
is visible on the first line of the display. The value editing procedure is presented in Figure 7-5.
Push the
Parameter Group Menu (G#)
. Locate the parameter
group desired by using the
and push the
its parameters. Use again the
the parameter
(P#)
you want to edit. From here you
can proceed in two different ways: Pushing the
takes you to the edit mode. As a sign of
this, the parameter value starts to blink. You can now change the value in two different manners:
1
Just set the new desired value with the
and confirm the change with the
. Consequently, the blinking stops and the new value is visible in the value field.
2
once again. Now you will be able to edit the value digit by digit. This
editing manner may come in handy, when a relatively greater or smaller value than that on the
display is desired. Confirm the change with the
The value will not change unless the Enter button is pushed. Pressing the
back to the previous menu.
Several parameters are locked, i.e. uneditable, when the drive is in RUN status. If you try to change the
value of such a parameter the text
*Locked*
will appear on the display. The frequency converter must be
stopped in order to edit these parameters.
The parameters values can also be locked using the function in menu M6 (see Chapter Parameter lock
(P6.5.2)).
You can return to the
Main menu
anytime by pressing the
The basic application package "All in One+" includes seven applications with different sets of parameters.
You will find the parameter lists in the Application Section of this manual.
Once in the last parameter of a parameter group, you can move directly to the first parameter of that group
by pushing the
See the diagram for parameter value change procedure on page 74.