Technical data – TREND NX Variable Speed Drives User Manual
Page 40
TECHNICAL DATA
vacon • 23
24-hour support +358 (0)40 837 1150 • Email: [email protected]
4
4.4 Technical
data
Input voltage U
in
208…240V; 380…500V; 525…690V; –15%…+10%
Input frequency
45…66 Hz
Connection to mains
Once per minute or less
Mains
connection
Starting delay
2 s (FR4 to FR8); 5 s (FR9)
Output voltage
0—U
in
Continuous output
current
I
H
: Ambient temperature max. +50°C,
overload 1.5 x I
H
(1 min./10 min.)
I
L
: Ambient temperature max. +40°C,
overload 1.1 x I
L
(1 min./10 min.)
Starting current
I
S
for 2 s every 20 s
Output frequency
0…320 Hz (standard); 7200 Hz (special software)
Motor
connection
Frequency resolution
0.01 Hz (NXS); Application dependent (NXP)
Control method
Frequency control U/f
Open Loop Sensorless Vector Control
Closed Loop Vector Control (NXP only)
Switching frequency
(see parameter 2.6.9)
NX_2/NX_5:
NX_2:
NX_5:
NX_6:
Up to NX_0061: 1…16 kHz; Default: 10 kHz
NX_0075 and greater: 1...10 kHz; Def: 3.6 kHz
NX_0072 and greater: 1…6 kHz; Def: 3.6 kHz
1…6 kHz; Default: 1.5 kHz
Frequency reference
Analogue input
Panel reference
Resolution 0.1% (10-bit), accuracy ±1%
Resolution 0.01 Hz
Field weakening point
8…320 Hz
Acceleration time
0.1…3000 sec
Deceleration time
0.1…3000 sec
Control
characteristics
Braking torque
DC brake: 30% * T
N
(without brake option)
Ambient operating
temperature
–10°C (no frost)…+50°C: I
H
–10°C (no frost)…+40°C: I
L
–10°C (no frost)…+35°C: for IP54/Nema12 NX 520 5 and 416 6
Storage temperature –40°C…+70°C
Relative humidity
0 to 95% RH, non-condensing, non-corrosive,
no dripping water
Air quality:
-
chemical vapours
-
mechanical
particles
IEC 721-3-3, unit in operation, class 3C2
IEC 721-3-3, unit in operation, class 3S2
Altitude
100% load capacity (no derating) up to 1,000 m
1-% derating for each 100m above 1000.
Max. altitudes: NX_2: 3000m; NX_5: 3000m/2000m (corner-
grounded network); NX_6: 2000m
Vibration
EN50178/EN60068-2-6
5…150 Hz
Displacement amplitude 1 mm (peak) at 5…15.8 Hz (FR4…9)
Max acceleration amplitude 1 G at 15.8…150 Hz (FR4…FR9)
Displacement amplitude 0.25 mm (peak) at 5-31 Hz (FR10…12)
Max acceleration amplitude 0.25 G at 31…150 Hz (FR10…12)
Shock
EN50178, EN60068-2-27
UPS Drop Test (for applicable UPS weights)
Storage and shipping: max 15 G, 11 ms (in package)
Ambient
conditions
Enclosure class
IP21/NEMA1 standard in entire kW/HP range
IP54/NEMA12 option in entire kW/HP range
Note! Keypad required for IP54/NEMA12
(Continues on next page)