beautypg.com

Standalone units (fr10 to fr12), 11. also see to that the, Ab c – TREND NX Variable Speed Drives User Manual

Page 53

background image

36 • vacon

INSTALLATION

Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205

5

A

B

C

Type Cooling

air

required

[m

3

/h)

0004—0012 NX_2
0003—0012 NX_5

70

0017—0031 NX_2
0016—0031 NX_5
0004—0013 NX_6

190

0048—0061 NX_2
0038—0061 NX_5
0018—0034 NX_6

425

0075—0114 NX_2
0072—0105 NX_5
0041—0052 NX_6

425

0140—0205 NX_2
0140—0205 NX_5
0062—0100 NX_6

650

0261—0300 NX_2
0261—0300 NX_5
0125—0208 NX_6

1300

Table 5-11. Required cooling air

5.2.2

Standalone units (FR10 to FR12)

Mounting space dimensions

[mm]

A

B

C

800

200

20

Table 5-12. Mounting space dimensions

Type

Cooling air required

[m

3

/h)

0385—0520 5
0261—0416 6

2600

0650—0730 5
0460—0590 6

3900

0820—1030 5
0650—0820 6

5200

Table 5-13. Required cooling air








Figure 5-12. Installation space