DPSA
DIFFERENTIAL PRESSURE SWITCHES
FOR AIR CONDITIONING / VENTILATION, USER-ADJUSTABLE
PRODUCT DATA AND INSTALLATION INSTRUCTIONS
TECHNICAL SPECIFICATIONS
Max. operating pressure 5000
Pa
Pressure media
air, non-flammable gases, and
non-aggressive
gases
Pressure connections
two plastic tubes, outside
diameter: 6.0 mm (0.24”)
Switching capacity
1.5 A, (0.4) /250 Vac
Electrical connections
screw terminals or AMP
connectors, 6.3 x 0.8,
DIN
46244
Conduit entry M20x1.5
Protection class IP
54
Mounting lugs
integrated in bottom housing
(alternative: mounting angles)
Medium/ambient temp.
-20...+85 °C (-4…+185 °F)
Storage temperature
-40...+85 °C (-40…+185 °F)
Membrane material silicone
APPLICATION
Differential pressure switches e.g. for monitoring filter, fan,
fire damper, or air flow status of air handling systems.
BENEFITS
•
Switching-point easily adjustable with scale in Pascal;
•
Direction of M20x1.5 conduit entry can be rotated in
steps of 120°;
•
Only one screw needed for housing cover.
APPROVALS
•
CE approval according to low-voltage directive EEC
73/23;
• Switch
according to VDE 0630;
•
EC Gas Appliance Directive 90/396/EEC according to
DIN EN 1854 (Nov. 01, 1997)
CONTENTS OF DELIVERY
The delivery includes (in the case of individual packages)
the following parts:
•
1 DPSA Differential Pressure Switch
•
1 Data Sheet with installation information
•
1 duct kit, consisting of:
-
2 m (2 yds 6”) of hosing
-
2 joining pipes with four screws
OPERATING RANGES
type
US code
adjustment range
for upper trip
pressure*
switching
difference
(hysteresis)
DPSA 200
882001720
20...200 (Pa)
10 (Pa)
DPSA 400
882001730
40...400 (Pa)
20 (Pa)
DPSA 1000
882001740
200...1000 (Pa)
100 (Pa)
*The trip pressure refers to vertical mounting. In case of
horizontal mounting (with the cover pointing upwards), the
range values increase by 20 Pa (i.e. a setting of 40 Pa will
switch at 60 Pa). The unit should not be mounted face
down.
DIMENSIONS
See "Mounting/Einbau/Montage" on page 4.
DPSA Data Sheet TA200878INT Issue 1/C 30/07/07
1
MU0B-0073GE51 R0707
Document Outline
- TECHNICAL SPECIFICATIONS
- APPLICATION
- BENEFITS
- APPROVALS
- CONTENTS OF DELIVERY
- OPERATING RANGES
- DIMENSIONS
- TECHNISCHE DATEN
- ANWENDUNGEN
- VORTEILE
- ZULASSUNGEN
- LIEFERUMFANG
- BETRIEBSBEREICHE
- ABMESSUNGEN
- SPECIFICATIONS TECHNIQUES
- APPLICATION
- AVANTAGES
- CERTIFICATION
- CONTENU DE L'EMBALLAGE
- PLAGE D’UTILISATION
- DIMENSIONS
- MOUNTING/EINBAU/MONTAGE
- DISPOSAL