beautypg.com

Section 4: accessories, 20 ma analog output – Fairbanks PC2250 Utility Software User Manual

Page 20

background image

6/12

20

51214 Rev. 7

Section 4: Accessories

4-20 mA Analog Output

16 bit Resolution and Monotonicity
0.01% Non-Linearity
Front Panel Programmable or via PC2250 utility software program
Passive (does not supply the voltage for the current loop)

Requirements:

External device must furnish 7 VDC to 40 VDC
The negative of the supply MUST be isolated from chassis ground
A separate power supply must be furnished for each FB2250

Wiring & Testing:

Follow these steps to text the 4-20 mA Analog Component.

1. Remove the four (4) screws fastening the back of the Indicator and open it.

2. Connect the Multimeter in series with the 4-20 mA Analog Output Loop, as noted

below.

TB1-1

(+) Power

TB1-2

(–) Power






If the device is passive, an auxiliary power supply must be used to supply the voltage

for the current loop. Wire it as shown.


FB2250 Condition

4-20 mA

analog output

FB2250 behind zero

3.5 mA

Weight below 4.20 LO

3.5 mA

Weight above 4.20 HI

24 mA

Program Mode

Locked on last 4-20 mA reading

Notes:
Loop power should be turned off whenever the FB2250 is turned off.

This manual is related to the following products: