Model jb2 - sizing and application data, Essential ordering information and data, Standard ul equipment and important options gas – Fulton VMP Webster Oil_Combo Burner User Manual

Page 8: Contact webster for complete information)

background image

(1)

STANDARD UL EQUIPMENT

AND IMPORTANT OPTIONS

Gas

No. 2 Oil

STANDARD UL EQUIPMENT

AND IMPORTANT OPTIONS

Gas

No. 2 Oil

Pressure Atomized

Air

Atomized

Pressure Atomized

Air

Atomized

General

Motor, Fan and Air Inlet Control

X

X

X

Gas Fuel

Main Manual Shutoff Valve

X

Air Flow Switch

X

X

X

Main Safety Shutoff Valve

X

(2)

Burner Mounted Control Panel,

Switch and Indicator Lights

X

X

X

Second Safety Shutoff Valve

X

Main Gas Regulator

X

Flame Safety Control

X

X

X

Gas Checking Valve

X

Ultra Violet Scanner

X

X

X

High and Low Gas Pressure Switches

X

Motor Controller (single phase voltage)

X

X

X

Metering Valve (modulating systems)

X

Motor Starter w/Overloads (3 PH volt)

X

X

X

Normally Open Vent Valve

Opt.

Fuel Selector Switch

Duel Fuel Burners Only

Ignition

Proven Gas Pilot Ignition

X

X

Oil Fuel

Oil Drawer Assembly with Diffuser

X

X

JB2-30 and JB2-50

X

X

X

Oil Nozzles

X

X

Pilot Solenoid Gas Valve

X

X

Integral Oil Pump (JB2-07 to JB2-20)

X

Pilot Gas Regulator & Manual Valve

X

X

Remote Oil Pump (JB2-30 to JB2-50)

X

Opt.

Pilot Gas Ignition Transformer

X

X

Two Safety Shutoff Valves

X

X

Direct Spark Oil Ignition

(3)

Low Air Atomizing Switch

X

Direct Spark Oil Ignition

Transformer

(3)

Low Oil Pressure Switch (STD when

using remote oil pump)

X

X

Options

Inverted Housing

X

X

X

Oil Pressure Gauge

X

X

Alternate Control Cabinet

Positioning

X

X

X

Oil Metering Valve (modulating

system)

X

X

Remote Control Panel

X

X

X

Future Gas Combustion Head

Opt.

Opt.

Fuel Metering CAM-NETIC II

X

X

X

Air Compressor

X

1. The configuration of each unit will vary with specific job requirements such as input rating, electrical specification and special agency approval codes.

The above chart shows those items standard to a basic burner plus a few options that may be added.

2. Indicator lights are “Power On”, “Call for Heat”, ”Fuel On” and ”Flame Fail” for hard wired panels. “Alarm”, “Low Water”, “Power”, “Call for Heat”, “Ignition

On”, and “Fuel On” for circuit board panels.

3. Maximum rate for direct spark is 20 GPH at low fire or 35 GPH at high fire. (standard on straight oil burners, pressure atomized)

Model JB2 - Sizing and Application Data

(contact Webster for complete information)

Model

Number

Maximum

Furnace

Pressure

Burner Firing

Capability Range

Burner

Motor

HP

Gas Train

Oil Pump Motor HP

Air

Compressor

Motor HP

Pipe Size

(3) Inlet Press (in wc)

Pressure

Atomizing

Air

Atomizing

Gas scfh

#2 Oil gph

LFS, LHL

Modulation

JB2-07

2

900 / 2800

10 / 20

3/4

1 1/2”

10 / 14”

13”

Integral

N/A

N/A

JB2-10

2

900 / 3500

10 / 25

1

2”

8 / 14”

9 / 14”

Integral

Optional

2

JB2-15

2

900 / 3500

10 / 25

1 1/2

2”

8 / 14”

9 / 14”

Integral

Optional

2

JB2-20

2

1200 / 4200

12 / 30

2

2”

(4)

12 / 14”

(3)

13 / 14”

Integral

Optional

2

JB2-30

2.5

1200 / 5300

12 / 37.8

3

2 1/2”

N/A

13 / 14”

3/4

Optional

2

JB2-50

2.5

1200 / 6000

12 / 42.8

5

2 1/2”

N/A

2-5 psi

3/4

Optional

2

3. Lower pressures may apply to reduced inputs. 4. 11-14” with IRI and LFS or LHL. 12-14” with IRI and modulation.

The above maximum ratings are based on 0 furnace pressure, an altitude of 1000 feet, 90oF air temperature and 60 HZ electrical supply. Use the follow-

ing corrections for higher temperatures and altitude. Capacity decreases by 17% for 50 Hertz.

Capacity decreases by 4% for each 1000 feet above 1000 foot altitude.

Capacity decreases by 6% for each 1 inch of furnace pressure.

Capacity decreases by 2% for each 10oF increase in air temperature over 90oF.

Gas input ratings based on 1000 BTU/cu ft. and 0.64 specific gravity. Sizes and pressure will vary with different gas properties.

Oil input ratings are based on 140,000 BTU/gal. for ASTM #2 fuel oil.

The vessel draft must be between -0.1 and +0.1 wc.

Essential Ordering Information and Data:

Power Supply - Confirm 120-60-1 for control circuit and electrical supply for burner motor(s) (voltage, frequency and phase).

Describe Boiler or Heater to be Fired - Including the manufacturer, model number, furnace pressure and furnace size.

Firing Rate - Define firing rates in MBH for gas and GPH for oil.

Fuel to be Burned - Type of gas and/or oil, including the BTU value.

Approval Agency - UL, FM, IRI (GE GAP), CSD-1, NFPA, Mil spec and local codes, if applicable.

Flame Safety Control Preferred - Honeywell or Fireye controls. Gas Train Components Preferred - ASCO/ITT, Honeywell or Landis

Control System - ON-OFF, Low Fire Start, Low High Low, Modulation, Posi-Control. Required Options - Mounting plate, limit controls, etc.

Model JB2 - Specification Data (6000 MBH Maximum Input)

Page 8

Specification

JB Manual