COMBUSTION AIR CONTROL

Panel

Adjusting

Screw

Air Proving

Switch

AIR FLOW INTERLOCKING SWITCH

2. AIR PROVING SWITCH

The air proving switch has been adjusted at the factory

for an initial setting. If the switch trips during initial start-

up, turn the adjustment screw ccw two full turns to re-

duce the trip pressure setting.

3. TYPICAL AIR AND FUEL ADJUSTMENT LOCATIONS

4. Fuel Cam Adjustments (if applicable)

The fuel cam needs to be checked for correct travel

and alignment. Positions can change during shipment

and installation and they must be reviewed prior to

startup. The fuel cams are mounted to the ends of the

jackshaft assembly. A cam follower link follows the profile

established by the

adjusting screws and drives the fuel

valve. A thin metal band is used between the screw and

cam follower to provide a smooth profile. The adjusting

screws are backed by compressed nylon inserts, which

provide a resistance to turning.
The cam (Figure G-3) should be checked for the following

conditions:

a. At the low fire position, the roller should be between

the first two adjusting screws. If not, adjust the position

of the cam accordingly, making sure to maintain the same

low fire fuel valve position.

b. When the linkage is modulated from low to high fire,

the roller must stay in the center of the adjusting screws

within 1/8”. If needed, the two cam set screws can be

loosened and the cam moved to center it on the roller.

c. At high fire, the roller should be between the last two

adjusting screws.

d. The adjusting screws should form a smooth contour

with no jumps between the screws.

e. In preparation of startup, the retention plate can

be removed temporarily to make it easier to adjust the

screws.
THE RETENTION PLATE MUST BE REPLACED WHEN

SETUP IS COMPLETE.
If the unit is equipped with a parallel positioning system

(linkageless), the control valves can be positioned and

operated in a similar manner, but accomplished through

the controller. Refer to the instruction manual for details.

CAUTION

LINKAGE AND ACTUATOR MOUNTINGS CAN BE BENT

OR MOVED DURING SHIPMENT AND INSTALLATION.

THEY MUST BE CHECKED PRIOR TO OPERATION AND

ANY FAULTS CORRECTED. FAILURE TO CORRECT A

MISALIGNED CONTROL WILL RESULT IN PREMATURE

FAILURE.

Page 29

Initial Settings

JB Manual