No.

System

Cause

Correction

1

No Ignition

Electrode is grounded. Porcelain is cracked.

Replace

(lack of spark)

Improperly positioned electrode

Recheck dimensions

Loose ignition wire connection

Reconnect or tighten

Defective ignition transformer

Check transformer, replace

2

No Ignition

Lack of fuel, no gas pressure, closed fuel valve

Check fuel supply and valves

(spark, no flame)

No voltage to pilot solenoid

Check electrical connections

Defective pilot solenoid valve

Replace

Incorrect location of pilot

Check location of pilot

Improper raw gas tube position

Check location of raw gas tube

Improperly positioned electrodes

Recheck dimensions

Too much combustion air flow

Check air damper position

3

Pilot not detected

Scanner tube not positioned correctly

Check location of scanner tube

(flame present)

Scanner tube dirty or wet (oil film)

Clean scanner tube / scanner

Scanner or amplifier faulty

Replace

Pilot improperly positioned

Check pilot position

Incorrect gas pressure to pilot

Readjust pressure

Combustion air flow rate too high

Readjust damper

4

No main gas flame

Weak scanner signal

Clean scanner lens and tube

(pilot OK)

Damper or fuel control valve setting incorrect

Readjust

Fuel valve(s) not opening

Check wiring to valves

5

No main oil flame

Weak scanner signal

Clean scanner lens and tube

(pilot OK)

Damper or fuel control valve setting incorrect

Readjust

Fuel valve(s) not opening

Check wiring to valves

Oil nozzle or line obstructed

Check nozzle and lines, clean

No atomizing air pressure

Check compressor wiring

Compressor pressure too low or high

Readjust

Burner not level, oil is draining into vessel

Check level, adjust as required.

6

Burner stays at low fire

Manual pot in low fire position (low fire hold)

Readjust to high fire position

Manual-auto switch or low fire hold switch in wrong position

Change position of switch

Modulating Control or Lo-Hi-Lo Control

Check wiring or replace

Loose linkage

Readjust and tighten

Binding linkage or valve

Readjust or replace

7

Burner shuts down

Loose electrical connection

Check and tighten connections

during operation

Loss of fuel supply

Replenish fuel supply

Limit switch breaks (opens)

Readjust limit switch

8

Burner does not start

Main disconnect switch is open

Close switch

Loose electrical connection

Check electrical connections

Operating controls are tripped

Check and reset operating limits

High or low fuel pressure

Check fuel supply - reset switches

9

High CO at low fire

Improper excess air level

Readjust excess air

(firing gas)

Input too low for burner components

Check input, compare to rating label

Page 42

Troubleshooting

JB Manual

J. TROUBLESHOOTING