beautypg.com

F. fuel systems, A” - on - off, L” - low fire start or “h” - low - hi - low – Fulton VMP Webster Oil_Combo Burner User Manual

Page 20: Pressure atomized oil systems

background image

Page 20

Fuel Systems

JB Manual

F. FUEL SYSTEMS

The JB burner can be equipped with a wide range of fuel and operating systems to control the fuel, air, modulation

and pilots. This section describes how these systems operate. Burner start-up is expected to be done by service per-

sonnel who are qualified in the basics of mechanical know-how. The following illustrations and information is supplied

to identify the various fuel; air and ignition devices that have

Adjustment Features. All adjustments can be done with

common place tools normally carried by burner and boiler service personnel.

NOTE

Refer to the bulletins included in the manufacturer’s data section of the burner instructions manual for items shown

below.

1. Pressure atomized oil systems

“A” - On - Off

Field Piped

Check Valve

Suction

Supply Line

Shutoff Valve

By Others

Strainer

Check

Valve

Gauge Port

Oil Pump

Adjustment

Return to Tank

(No Manual Valves

in this line)

Main Oil

Solenoid Valve

Oil Nozzle

Safety Oil

Solenoid Valve

By Others

Unless Specified on Order

Notes & Options

These Lines are Field

Piped if a Remote

Pump is Used

1

1

1

“L” - Low Fire Start or “H” - Low - Hi - Low

Shutoff Valve

Check

Valve

Field Piped

Strainer

By Others

Unless Specified on Order

Suction

Supply Line

Return to Tank

(No Manual Valves

in this line)

Check Valve

By Others

Main Oil

Solenoid

Valve

Oil Nozzle

Safety Oil

Solenoid Valve

Gauge Port

Oil Pump

Adjustment

1

1

2

High Fire Cylinder

Louver Actuator

Low Fire Bypass Regulator

(Adjustment for Low Fire

Approx. 100 - 125 PSI)

N.O. Low Fire

Bypass Oil Valve

Low Oil

Press. Sw

.

2 or 3 1 (IN)

(out)

Notes & Options

These Lines are Field

Piped if a Remote Pump

is Used
Required Above 20 GPH

if a Remote Pump is Used

1

IN

IN

Field Piped

2