beautypg.com

H. ignition systems – Fulton VMP Webster Oil_Combo Burner User Manual

Page 30

background image

H. IGNITION SYSTEMS

Page 30

Ignition Systems

JB Manual

1. Gas Pilot Assembly

A crucial part of reliable burner operation is a dependable

pilot, which must be properly adjusted and kept clean. A gas

pilot is standard for all models except JB1 through JB2-20

straight oil pressure atomizing burners which have direct

spark ignition as standard. The following illustrations show

the typical configuration and nominal adjustment parame-

ters of each pilot.
Figure H-1 showns the JB1 & JB2 gas pilot. Figure H-2

shows the JB3 gas pilot. Figure H-3 shows how the pilots

are positioned in the burner drawer.
Pilot gas pressure should be measured at the 1/8” port locat-

ed on the downstream side of the last pilot solenoid valve.
2. Oil Nozzle Positiion, Direct Spark Oil.

Figures H-5 and H-6 show the position of direct spark igni-

tion and nozzle positions. These are initial settings and will

be adjusted at start-up.
3. Air Damper Position

On a straight gas burner, the air damper should be open

about 1/4” at low fire and close to full open at high fire. In

Figure H-2 JB3 PILOT ASSEMBLY

Natural Gas Pressure;

4 - 6” wc

LP Gas Pressure;

1.5 - 2.5” wc

some applications, the pilot requires an orifice in the pilot

gas supply line. With the exception of the JB3, this ori-

fice is located external of the blower housing.
The pilot to diffuser dimension is the distance of the face

of the pilot to the outer diameter of the diffuser.
For an oil or combination burner, the air damper should

be open about 3/8” at low fire and close to full open at

high fire.
4. Gas Modualting Control Valve Position

The gas valve should be open about 10% at low fire and

stroked to abput 60% open at high fire.
5. Oil Modulatining Control Valve Position.

For pressure atomizing, the low fire position should be

adjusted to get the correct low fire presure, as stated

on the rating label. Typically, this would be 100 psi for

simplex systems and 65 psi for return flow nozzles. The

high fire position should be about 45o to 60o travel from

low fire.
For air atomizing, the low fire should be on about #2 po-

sition and the high fire should be about the #8 position.

Electrode

Pilot

Electrode Clamp

Figure H-1

JB1 & JB2 Gas Pilot

Spark

Gap = 1/16”

Note: Required 2 1/2” - 3” wc

pressure for natural gas ans 1/2”

- 2” for LP, as measured at the

last solenoid in the pilot train.