beautypg.com

Fulton VMP Webster Oil_Combo Burner User Manual

Page 41

background image

the location of the pilot and scanner, as shown in section

“H”. This may also indicate a faulty scanner or amplifier.
17. Burner Shutdown
Normal operation of the burner will allow the operating

controls to shut the burner down when the load demand is

satisfied. If the burner needs to be shut down for any rea-

son, the “ON-OFF” switch can be used to quickly turn the

burner off. This will instantly cause the fuel valves to close

and start a post purge cycle to remove any unburned fuel

from the vessel.
In an emergency shutdown, all fuel and electrical power

should be de-energized or turned off to secure the burner.

This would include the main power disconnect, the manu-

al gas shutoff valve at the drop down line and if equipped,

the manual oil valve to the nozzle.
It is recommended that the burner be manually driven to

low fire before turning the burner off, as this reduces the

dynamic and thermal stress. If the burner will remain off

for some time, the manual fuel valves, fuel pumps and

power supply should be turned off.

CAUTION

ALWAYS KEEP THE FUEL SUPPLY VALVE SHUT OFF WHEN THE

BURNER IS SHUT DOWN FOR AN EXTENDED PERIOD OF TIME.

18. Restarting after Extended Shutdown
Extended shutdowns require the same startup process as

those outlined above. In addition, the following advanced

cleaning must be done,

a. The air atomized oil nozzle should be removed and

cleaned, if pressure atomized they should be replaced.

Use care in cleaning to preserve the sharp edges of the

nozzle, which are required to maintain good atomization.

b. The oil filter and strainer must be removed and cleaned

prior to starting.

CAUTION

DO NOT START THE BURNER UNLESS ALL CLEANOUT DOORS

ARE SECURED IN PLACE.

Page 41

Startup and Operating Adjustments

JB Manual