Installation / Canadian Installations

JB Manual

Drip Leg

Manual Gas

Shutoff Valve

Gas Pressure

Regulator

Low Gas

Pressure

Switch

Shutoff

Valve

Shutoff

Valve

High Gas

Pressure

Switch

Normally

open vent

valve

Leak Test

Valve

Pilot Gas

Pressure

Regulator

Pilot Solenoid

Valve

Pilot

Shutoff

Valve

Figure C-1

Typical Gas Piping

Gas Supply

Burner

If applicable, Webster

supplied gas train

D. SPECIAL INSTRUCTIONS FOR CANADIAN INSTALLATIONS

1. The installation of a burner shall be in accordance with

the regulations of the provincial installation requirements,

or in their absence, the following shall govern:

Gas Burners--CGAB149.1 and CGAB149.2

Oil Burners--CSA Standard B139

Authorities having jurisdiction should be consulted before

installations are made.

2. All electrical wiring shall be done in accordance with

Chart C-2

Chart C-3

FURNACE DIAMETER - INCHES

Width

Height - Floor to Center of Burner

Length

Length

Diameter

TYPICAL COMBUSTION CHAMBER SIZE

FOR FIREBOX BOILERS, WATERTUBE &

CAST IRON SECTIONAL TYPES

TYPICAL COMBUSTION CHAMBER SIZE

FOR SCOTCH MARINE FIRETUBE BOILERS

the Canadian Electrical Code, Part I.
3. The installer shall identify (label) the main electrical

power disconnect and the manual shut-off valve on the
gas and/or oil supply drop-line to the burner.

4. Oil and gas burning equipment shall be connected to

flues having sufficient draft at all times, to assure safe

and proper operation of the burner.