beautypg.com

L. care of the burner during extended shutdown, M. replacement parts, N. warranty validation & field start-up report – Fulton VMP Webster Oil_Combo Burner User Manual

Page 48

background image

Page 48

Extended Shutdown / Replacement Parts / Start-Up Report

JB Manual

be stocked to support uninterrupted burner operation.

Pilot Electrode

Blower Wheel

Oil Pump (if oil burner)

Oil Pump Coupling (if oil burner)

Pilot Ignition Transformer

Oil Ignition Transformer (if used)

Gas Pilot Solenoid Valve

Flame Scanner

Items with greater life expectancy and/or greater dollar val-

ue, such as flame safety controls, main gas or oil valves and

blower motors should be obtained from your local Webster

representative when a need arises.

L. CARE OF THE BURNER DURING EXTENDED SHUTDOWN

Heating equipment is oftentimes located in an environ-

ment conducive to corrosion and general deterioration if

not properly protected and periodically checked, especially

during an extended period of shut down. The following

procedures should be followed if the burner is going to be

placed out of service even for a short period of time.

1. Turn the main manual fuel valve OFF.

CAUTION

Always keep the main fuel valve(s)

OFF if the burner

is shut down for an extended period of time.

2. Turn off the main electrical disconnect to the burner

OFF. Follow tagout / lockout procedures.

M. REPLACEMENT PARTS

3. Place a notification tag or label at the main manual

fuel valve giving reason for shutdown. Follow tagout /

lockout procedures.

4. If the burner is in an area subject to sweating and

condensation, cover the control cabinet and electrical de-

vises with plastic and secure with twine or tape.

5. Should the burner be out of service for more than thirty

(30) days, a complete operational safety check must be

made at the time of restart. The restart must be treated

as a new burner start-up (see burner start-up section in

this manual).

6. The oil nozzle(s), if pressure atomized should be re-

placed. If air atomized, clean the nozzle with cleaning

fluid and a soft brush.

An illustrated parts drawing is included within the Burner

Instructions Manual to aid in parts identification. The noun

name of the part needed should be established from the

drawing, then the part number can be obtained from the

burner material list contained in the Burner Instructions

and Service Manual.

NOTE

Always give Webster Engineering Serial

Number and/or UL Serial Number when

ordering parts.

N. WARRANTY VALIDATION & FIELD START-UP REPORT

As a final step, forward the top copy of the Warranty Valida-

tion and Field Startup Report, Form 113, to:

WEBSTER ENGINEERING & MFG. CO., LLC, 619 Indus-
trial Road, Winfield, KS 67156.

WEBSTER Series JB Burners are listed by Un-

derwriters Laboratories, Inc. (U.L.). Also by the

State of Massachusetts Fire Marshall, City of New

York Board of Standards and Appeals, State of

Minnesota, and can be packaged to meet specific

requirements of CSD-1, GE GAP, IRI, FM, NFPA,

MIL or other special insurance or local code re-

quirements.