beautypg.com

Fulton VMP Webster Oil_Combo Burner User Manual

Page 34

background image

equipped with Posi-Control can be adjusted for individual air

and FGR settings on both fuels and can easily handle these

variations, even with lower NOx levels. Linkage burners op-

erating at 30 ppm NOx (natural gas) are equipped with a

potentiometer in the control panel that will allow the shut-off

valve to partially open and allows a small amount of FGR to

flow when firing oil. This keeps the oil inputs close to the gas

input (lower FGR rates increases the combustion air rate).

The oil combustion is generally better when FGR is used at

low rates resulting is a lower NOx level. Linkage levels with

NOx levels under 30 ppm will also use a multiple modulation

motor to provide separate gas and oil low fire and high fire

positions.
Linkage dual fuel units may also be equipped with the op-

tional multiple set point (Landis) modulation motor in addition

to the above potentiometer. This motor allows for different

low and high fire settings on gas vs oil to obtain the correct

airflow for each fuel and optimize the turndown on gas.
The quantity of recirculated flue gas can be adjusted with the

inlet tube on the FGR line. To reduce the quantity of FGR,

push the tube into the FGR line (loosen the two set screws

to adjust the position of the tube, and tighten when done).

Moving the tube into the air stream will increase the quantity

of FGR. An access cover is provided opposite the FGR line

for this adjustment.
On a dual fuel unit, the natural gas should be done first to

properly set the FGR inlet tube. Once gas is setup, oil can

be set.
For dual fuel linkage systems, the following guidelines

should be used:

• A 60 ppm system can be adjusted with the same FGR rate

on both fuels. The FGR control valve is set on gas and oil

follows that setting.

• A 30 ppm system uses the FGR limiting potentiometer

(located in the control panel) to obtain a partial flow of FGR

when firing oil. The FGR control valve is set when firing

gas. The FGR limiting potentiometer is adjusted to improve

combustion but not cause instability. The combustion needs

to be checked at several firing rates.

• Under 30 ppm, separate gas and oil operating points are

established in the modulating motor.

Parallel positioning

(linkageless) systems allow all of the valves to be positioned

independently for each fuel. For this reason, the setup se-

quence can be more flexible.
5. Burner Drawer Adjustments
The burner drawer has several adjustments built into the de-

sign that allow the combustion to be tuned. While this can

simplify the combustion tuning process, care must be used

to retain the relative position of other components during this

sequence. If these adjustments are required, follow the se-

quence listed to perform the adjustments.
Before any adjustments are made, the position of each com-

ponent must be marked. A felt tip pen or a combination of

masking tape and another type of pen can be used.

• Mark the distance of the oil gun tube from the backplate.

• Mark the distance of the gas pilot line to the backplate.

a. To adjust the diffuser to inner fire cylinder dimen-

sion:

• Measure the dimension from the backplate to the end

of the oil gun tube. This dimension, along with the initial

position will determine the limit of the adjustment. For

example, if the diffuser is 1 inch behind the fire end of

the inner fire cylinder, then it can be adjusted in 3/4 inch

or out 1/2 inch to stay within the limits of 1/4 inch to 1 1/2

inch diffuser to fire end of the inner fire cylinder dimen-

sion.

• Loosen the two setscrews locking the pilot gas line

and gun tube to the backplate.

• Adjust the diffuser by moving the oil gun tube in and

out the amount determined above. When the best posi-

tion is found, lock into place with the two setscrews on

the oil and pilot tubes.

b. To adjust the oil nozzle to diffuser position:

• Adjust the oil nozzle to obtain the best combustion.

• Watch for spray back on the diffuser when the oil noz-

zle is pulled too far back. The flame may appear good

but carbon will quickly develop on the diffuser.

• The drawer assembly must be removed to adjust the

oil nozzle to diffuser position.

The burner drawer must be removed for access to com-

ponents, follow the following steps:

a. Disconnect the gas pilot line. Move the pilot line so

the drawer can be pulled out without interference.

b. If equipped with oil, disconnect the oil line(s), and

move the oil line out of the way to allow the drawer to

be pulled.

c. Loosen and remove the screws on the burner draw-

er.

d. Disconnect the ignition cable from the drawer assem-

bly. It is attached with a snap-on fitting.

e. Pull the drawer out, holding the drawer centered in

the opening to prevent it from hanging up while being

pulled out.

f. Disconnect the scanner by screwing it off of the scan-

ner tube. In some cases, the scanner simply pulls out,

with a spring tension. Secure the scanner so that it is

protected from shock.

g. Set the drawer down horizontally, do not set it on the

diffuser as it may flatten some fins or change positions.
To re-install the burner drawer, simply work the proce-

dure in reverse.
6. Single Fuel Setups
Single fuel burners can be adjusted following the proce-

dures outlined in Section 10 for gas firing; Section 11 for

pressure atomized oil, Section 12 for Air atomized #2 oil

and Section 13 for heavy oil firing.
The procedures for each of the systems (linkage, cams,

FGR) must be completely understood and followed as

part of the setup process.
7. Combination Gas and Pressure Atomized Oil

Page 34

Startup and Operating Adjustments

JB Manual