Model jb3 - sizing and application data, Essential ordering information and data, Standard ul equipment and important options gas – Fulton VMP Webster Oil_Combo Burner User Manual
Page 10: Contact webster for complete information)

(1)
STANDARD UL
EQUIPMENT
AND IMPORTANT OPTIONS
Gas
No. 2 Oil
No. 4 - 6 Oil Air
Atomized
STANDARD UL EQUIPMENT
AND IMPORTANT OPTIONS
Gas
No. 2 Oil
N0. 4 - 6 Oil Air
Atomized
Pressure At
om
iz
ed
Air
At
om
iz
ed
Pressure At
om
iz
ed
Air
At
om
iz
ed
General
Motor, Fan and Air Inlet Control
X
X
X
X
Gas Fuel
Main Manual Shutoff Valve
X
Air Flow Switch
X
X
X
X
Main Safety Shutoff Valve
X
(2)
Burner Mounted Control Panel,
Switch and Four Indicator Lights
X
X
X
X
Second Safety Shutoff Valve
X
Main Gas Regulator
X
Flame Safety Control
X
X
X
X
Gas Checking Valve
X
Ultra Violet Scanner
X
X
X
X
High and Low Gas Pressure Switches
X
Motor Starter with Overloads
X
X
X
X
Metering Valve (modulating systems)
X
Fuel Selector Switch
Duel Fuel Burners Only
Normal Open Vent Valve (above
12,500 MBH)
X
Ignition
Proven Gas Pilot Ignition
X
X
X
Oil Fuel
Oil Drawer Assembly with Diffuser
X
X
X
Pilot Solenoid Gas Valve
X
X
X
Oil Nozzles
X
X
X
Pilot Gas Regulator & Manual Valve
X
X
X
Oil Heater with Integral Thermostat
X
Pilot Gas Ignition Transformer
X
X
X
Remote Oil Pump
X
Opt.
Opt.
Two Safety Shutoff Valves
X
X
X
High Oil Temperature Switch
X
Low Air Atomizing Switch
X
Options
Inverted Housing
X
X
X
X
Low Oil Pressure Switch
X
X
X
Alternate Control Cabinet Positioning
X
X
X
X
Oil Pressure Gauge
X
X
X
Remote Control Panel
X
X
X
X
Oil Metering Valve
X
X
X
Fuel Metering CAM-NETIC II
X
X
X
X
Future Gas Combustion Head
Opt.
Opt.
Opt.
Posi-Control
X
X
X
X
Air Compressor
X
X
1. The configuration of each unit will vary with specific job requirements such as input rating, electrical specification and special agency approval codes.
The above chart shows those items standard to a basic burner plus a few options that may be added.
2. Indicator lights are “Power On”, “Call for Heat”, ”Fuel On” and ”Flame Fail”.
Model JB3 - Sizing and Application Data
(contact Webster for complete information)
Model
Number
Maximum
Furnace
Pressure
Burner Firing Capability Range
Burner
Motor
HP
Gas Train
#2 Oil Pump Motor HP
#4 - 6
Pump
Motor HP
Air
Compressor
Motor HP
Pipe
Size
Inlet
Press
Pressure
Atomizing
Air
Atomizing
Gas scfh
#2 Oil
gph
#4-6
Oil gph
JB3-30
3.5
1400 / 6300
10.2 / 45
10 / 42
3
2 1/2”
12 / 27”
1
Optional
Optional
2
JB3-50
3.5
1400 / 8300
11 / 59.2
10 / 55.3
5
3”
15 / 27”
1 1/2
Optional
Optional
2
JB3-75
3.5
1600 / 10500
12.3 / 75
11 / 70
7 1/2
3”
23 / 27”
1
Optional
Optional
2
JB3-100
3.5
1800 / 12600
20.3 / 90
12 / 84
10
3”
2-5 psi
1
Optional
Optional
2
The above maximum ratings are based on 0 furnace pressure, an altitude of 1000 feet, 90oF air temperature and 60 HZ electrical supply. Use the follow-
ing corrections for higher temperatures and altitude. Capacity by 17% for 50 Hertz.
Capacity decreases by 4% for each 1000 feet above 1000 foot altitude.
Capacity decreases by 6% for each 1 inch of furnace pressure.
Capacity decreases by 2% for each 10oF increase in air temperature over 90oF.
Gas input ratings based on 1000 BTU/cu ft. and 0.64 specific gravity. Sizes and pressure will vary with gas.
Oil input ratings are based on 140,000 BTU/gal. for ASTM #2 fuel oil and 150,000 BTU/gal for ASTM #4-6 fuel oil.
The vessel draft must be between -0.1 and +0.1 wc.
Essential Ordering Information and Data:
Power Supply - Confirm 120-60-1 for control circuit and electrical supply for burner motor(s) (voltage, frequency and phase).
Describe Boiler or Heater to be Fired - Including the manufacturer, model number, furnace pressure and furnace size.
Firing Rate - Define firing rates in MBH for gas and GPH for oil.
Fuel to be Burned - Type of gas and/or oil, including the BTU value.
Approval Agency - UL, FM, IRI (GE GAP), CSD-1, NFPA, Mil spec and local codes, if applicable.
Flame Safety Control Preferred - Honeywell or Fireye controls.
Gas Train Components Preferred - ASCO/ITT, Honeywell or Landis
Control System - ON-OFF, Low Fire Start, Low High Low, Modulation, Posi-Control
Required Options - Mounting plate, operating controls, limit controls, etc.
Model JB3 - Specification Data (12,600 MBH Maximum Input)
Page 10
Specification
JB Manual